35 kV变压器微机差动保护误动现象分析  被引量:1

Analysis of Misoperation of Microcomputer Differential Protection for 35 kV Transformer

在线阅读下载全文

作  者:吴健[1] WU JIan(Hydroelectric Power Station of Henan Oilfield,Nanyang 473132,China)

机构地区:[1]河南石油勘探局水电厂,河南南阳473132

出  处:《电工技术》2021年第14期124-126,共3页Electric Engineering

摘  要:微机保护较抽象,尤其对于Y,D接线方式的变压器,其高低压侧电流存在相位差,而差动保护为分相差动,所以需要对高低压侧电流相位进行角度误差补偿校正。对Yd-11联接组别变压器的微机差动保护原理进行分析,解释在实际工作中高压侧CT二次线两相换位造成差动保护误动的原因。Microcomputer protection is abstract, especially for transformers with Y and D wiring. There is a phase difference between the high and low voltage side currents, and the differential protection is a split phase differential. It is necessary to perform angle error compensation correction on the high and low voltage side current phase. The principle of the microcomputer differential protection of Yd-11 connection group transformers is analyzed, and the reason for the misoperation of the differential protection caused by the two-phase transposition of the high-voltage side CT secondary line in actual work is explained.

关 键 词:变压器 微机型保护 差动 误动 

分 类 号:TM406[电气工程—电器]

 