检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
作 者:薛永端[1] 任伟[1] 唐毅 徐丙垠[3] XUE Yongduan;REN Wei;TANG Yi;XU Bingyin(College of New Energy,China University of Petroleum(East China),Qingdao 266580,China;State Grid Shandong Power Dispatching and Control Center,Jinan 250001,China;Smart Grid Research Institute,Shandong University of Technology,Zibo 255049,China)
机构地区:[1]中国石油大学(华东)新能源学院,山东省青岛市266580 [2]国网山东电力调度控制中心,山东省济南市250001 [3]山东理工大学智能电网研究院,山东省淄博市255049
出 处:《电力系统自动化》2021年第18期122-130,共9页Automation of Electric Power Systems
基 金:国家自然科学基金资助项目(52077221)。
摘 要:受环境因素及电弧自身燃、熄弧特性影响,间歇接地故障燃弧持续时间常小于保护动作时限,传统接地故障保护难以有效动作。分析小电阻接地系统接地故障特征,并比较出线与中性点零序电流关系,基于接地电阻器在故障期间发热、故障消失后散热的热稳定原理,提出一种中性点小电阻接地系统间歇接地故障保护方法。该方法利用零序电流构造故障期间的发热特征能量,利用热量差构造故障消失后的散热特征能量,发热特征能量越限后保护动作。经仿真与现场录波数据验证可知,该方法不易受故障间隔时间与过渡电阻影响,可作为现有中性点小电阻接地系统的出线后备保护,提高系统运行可靠性。Affected by environmental factors and characteristics of arc ignition and extinction,arc duration of intermittent grounding faults is generally shorter than the protection operate time.Therefore,it is difficult for traditional protection to operate effectively.In this paper,characteristics of grounding faults in low resistance neutral grounded systems are analyzed.Then,the relationships between zero-sequence current of the feeder lines and the neutral point are compared.Based on the thermal stability principle that grounding resistors generate heat during faults and dissipate heat after faults,a protection method is proposed for intermittent grounding faults in low resistance neutral grounded systems.In this method,the characteristic energy of thermal accumulation during the faults is constructed using zero sequence current,and the characteristic energy of thermal dissipation after the faults is constructed using the difference of heat.The protection operates when characteristic energy of thermal accumulation exceeds the operation setting value.It is verified by simulation and field record data that this method is not likely affected by fault interval time and transition resistance,which can be used as backup protection for feeder lines in low resistance neutral grounded systems to improve system operation reliability.
关 键 词:中性点小电阻接地系统 间歇接地故障 零序电流 接地电阻器 热稳定原理
分 类 号:TM862[电气工程—高电压与绝缘技术]
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:216.73.216.42