高压穿墙套管带电检测诊断及应对措施  

Diagnosis and Countermeasures of Charged Detection in High-Voltage Through-Wall Bushing

在线阅读下载全文

作  者:何书迪 周新军 李毅 唐晓峰 严敏敏 HE Shudi;ZHOU Xinjun;LI Yi;TANG Xiaofeng;YAN Minmin(State Grid Yongzhou Power Supply Company,Yongzhou 425000,China)

机构地区:[1]国网湖南省电力有限公司永州供电分公司,湖南永州425000

出  处:《湖南电力》2021年第5期105-108,共4页Hunan Electric Power

摘  要:分析不停电条件下发现变电站内高压穿墙套管异常放电的方法,验证了红外精准测温、超声波局放检测等带电检测手段对高压穿墙套管异常放电的灵敏性与可靠性,避免了变压器差动范围跳闸事故,同时定制出全密封型圆铜棒瓷质穿墙套管,有效解决了潮气入侵穿墙套管导致设备异常放电等问题。This article analyzes the method of abnormal discharge of high-voltage through-wall bushings in substations under uninterrupted power condition,verifies the sensitivity and reliability of infrared accurate temperature measurement,ultrasonic local discharge detection and other live detection methods to abnormal discharge of high voltage casing,which can avoid tripping accidents in the differential range of the transformer.And a fully sealed round copper rod porcelain through-wall bushing is customized,which can solve the problem of abnormal discharge of equipment caused by moisture invading the through-wall bushing.

关 键 词:穿墙套管 带电检测 受潮 全密封 

分 类 号:TM216􀆰[一般工业技术—材料科学与工程]

 