检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
作 者:柳金淼 刘辉 陈鑫浩 郑乐奥 LIU Jinmiao;LIU Hui;CHEN Xinhao;ZHENG Leao(Zhejiang TENGEN Electric Co.,Ltd.,Whenzhou 325600,China)
机构地区:[1]浙江天正电气股份有限公司,浙江温州325600
出 处:《电工技术》2021年第18期109-111,共3页Electric Engineering
摘 要:介绍了中性线重叠原理,通过中性线重叠时间设计,阐述了中性线重叠结构的改进,可有效解决转换过程中,负载三相不平衡时断零产生的零地漂移电压和瞬态涌压,以提高电信和数据中心的服务器设备用电安全。The principle of neutral line overlapping and the improvement of the neutral overlapping structure are introduced.Through the neutral line overlapping time design,the zero-ground drift voltage and transient surge caused by the zero-breaking of the load when the three-phase load is unbalanced during the conversion process can be effectively solved,so as to improve the power safety of server equipment in telecommunications and data centers.