基于牵引供电线路保护死区问题的探讨和实践  

Discussion and Practice on Dead Zone of Traction Power Supply Line Protection

在线阅读下载全文

作  者:孙旭 SUN Xu(Jieyang Power Supply Bureau of Guangdong Power Grid Co.,Ltd.,Jieyang 522000,China)

机构地区:[1]广东电网有限责任公司揭阳供电局,广东揭阳522000

出  处:《电工技术》2021年第18期145-147,共3页Electric Engineering

摘  要:牵引供电线路与电力系统输电线路不同,前者使用的是交流两相,而变电站输出设备均为三相。由于保护配置及CT安装位置的原因,非供电相在变电站出线端可能存在保护死区,当发生非供电相单相接地故障时,母线差动保护及线路保护均不能快速动作切除故障。以一起牵引供电线路非供电相接地故障为例,分析牵引供电线路保护死区问题,并结合一、二次设备的配置,提出改进措施。Traction power supply lines are different from power system transmission lines.The former uses AC two-phase,while the output equipment of the substation is three-phase.Due to the protection configuration and CT installation location,the non-power supply phase may have a protection dead zone at the outlet end of the substation.When a single-phase ground fault occurs in a non-power supply phase,neither the bus differential protection nor the line protection can act quickly to remove the fault.Taking a grounding fault of non-power supply phase of traction power supply line as an example,the problem of protection dead zone of traction power supply line is analyzed.Combined with the configuration of primary and secondary equipment,the improvement measures are put forward.

关 键 词:牵引供电线路 非供电相 保护死区 

分 类 号:TM732[电气工程—电力系统及自动化]

 