检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
作 者:沈文英[1] 吴建军 缪进进 李子武 叶强 SHEN Wenying;WU Jianjun;MIAO Jinjin;LI Ziwu;YE Qiang(NR Electric Co.,Ltd.,Nanjing Jiangsu 210000,China)
机构地区:[1]南京南瑞继保电气有限公司,江苏南京210000
出 处:《湖北电力》2021年第4期94-99,共6页Hubei Electric Power
摘 要:通过主断路器断口闪络导致断路器爆炸的两个典型案例分析,认识闪络时电流电压变化特点。从理论上分析了闪络振荡最小电流,提出了闪络保护改进措施。建议增加500 kV和220 kV的断路器闪络失灵保护,可以在闪络后的两百多毫秒通过闪络失灵保护切除故障,有效减小断路器爆炸和主设备损坏的风险。This paper introduces the characteristics of current and voltage variation during flashover through analyzing two typical cases of breaker explosion caused by flashover of main circuit breaker,and then theoretically analyzes the minimum current during flashover oscillation,and puts forward the improvement measures of flashover protection.Finally,the paper suggests adding 500kV and 220kV circuit breaker flashover failure protection,where flashover failure protection can function to remove faults in over 200 milliseconds after flashover,effectively reducing the risk of breaker explosion and main equipment damage.
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:216.73.216.225