作 者:许婷苇 赵丽平[1] 林圣[1] 叶烨 Xu Tingwei;Zhao Liping;Lin Sheng;Ye Ye(School of Electrical Engineering, Southwest Jiaotong University, Chengdu 611756, Sichuan, China;State Grid Sichuan Maintenance Company,Chengdu 610041, Sichuan, China)
机构地区:[1]西南交通大学电气工程学院,四川成都611756 [2]国网四川省电力公司检修公司,四川成都610041
出 处:《四川电力技术》2021年第5期17-20,90,共5页Sichuan Electric Power Technology
基 金:四川省重点研发计划项目(2020YFG0063)。
摘 要:对于现有仅利用单一设备量测量信息进行故障判断的100 Hz保护,其动作响应存在一定的盲目性,在换流站交流区域故障时适应性不足。对此提出基于站域信息区分整流站直流区域故障和交流区域故障,实现100 Hz保护优化,赋予100 Hz保护识别整流站直流区域故障与交流区域故障的能力。基于100 Hz保护误动原因分析,提出换流母线基频负序电压与直流线路二次谐波电压的相关系数,构建整流站故障区域识别方法。仿真结果表明,该方法不受故障类型、故障位置、过渡电阻、故障初始角以及噪声干扰的影响,可靠性高。Aiming at the existing 100 Hz protection using only a single device measurement information for fault judgment,the action response of the protection is blind to a certain extent,and its adaptability is insufficient when the AC area of converter station fails.It is proposed to distinguish the DC area fault from the AC area fault of rectifier station based on station domain information,which realizes 100 Hz protection optimization and gives 100 Hz protection the ability to identify the DC area fault and the AC area fault of rectifier station.Based on the cause analysis of misoperation of 100 Hz protection,the correlation coefficient between the negative sequence voltage of converter bus fundamental frequency and the second harmonic voltage of DC line is proposed,and the fault area identification method of rectifier station is constructed.The simulation results show that the method is not affected by fault type,fault location,transition resistance,fault initial angle and noise interference,and has high reliability.
关 键 词:高压直流输电 100Hz保护 站域信息 故障区域 相关系数
分 类 号:TM712[电气工程—电力系统及自动化]
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:216.73.216.7