转速可控型房间空气调节器能效标识备案实验室间比对试验结果分析与评价  

Analysis and evaluation of comparison test results of energy efficiency label documented laboratories of variable speed room air conditioner

在线阅读下载全文

作  者:徐军 胡永胜 任道一 郑明宇 齐淑芳 Xu Jun;Hu Yongsheng;Ren Daoyi;Zheng Mingyu;Qi Shufang(Hefei General Machinery Research Institute Co.,Ltd)

机构地区:[1]合肥通用机械研究院有限公司

出  处:《制冷与空调》2021年第10期50-54,70,共6页Refrigeration and Air-Conditioning

摘  要:为了保证转速可控型房间空气调节器能效标识备案实验室间比对试验时的准确性,制备符合均匀性和稳定性要求的标准样机,采用稳健统计技术对参与比对的实验室的全年能源消耗效率(APF)检测结果进行统计与分析。结果表明:在比对的43家实验室中,40家实验室结果为满意、3家为不满意,说明目前转速可控型房间空气调节器能效标识备案实验室的数据一致性较好。In order to ensure the accuracy of the comparison test results of the energy efficiency label documented laboratories of variable speed room air conditioner,the criteria prototypes that satisfy the requirements of uniformity and stability are made.Using robust statistical techniques,the statistical analysis is conducted on the test results of annual performance factor(APF)of the participating laboratories.The results show that among the 43 laboratories that participate in the comparison,the results of 40 laboratories are satisfactory,while the results of 3 laboratories are unsatisfactory,which indicates that the current data consistency of the energy efficiency label documented laboratories of variable speed room air conditioners is good.

关 键 词:转速可控型房间空气调节器 能效标识备案实验室 均匀性 稳定性 

分 类 号:TP3[自动化与计算机技术—计算机科学与技术]

 