数据中心间接蒸发自然冷却空调系统在中国的适用性分析  被引量:7

Applicability Analysis of Indirect Free Cooling Air Conditioning System for China Data Center

在线阅读下载全文

作  者:褚俊杰 徐伟 霍慧敏 Chu Junjie;Xu Wei;Huo Huimin(Institute of Building Environment and Energy,China Academy of Building Research,Beijing,100013)

机构地区:[1]中国建筑科学研究院有限公司建筑环境与能源研究院,北京100013

出  处:《制冷与空调(四川)》2021年第5期725-732,共8页Refrigeration and Air Conditioning

基  金:国家重点研发计划“近零能耗建筑技术体系及关键技术开发”(2017YFC0702600);国家重点研发计划“藏区、西北及高原地区利用可再生能源采暖空调新技术”(2016YFC0700400)。

摘  要:首先基于最新的ASHRAE数据中心标准制作的中国自然冷却地图,直观地说明中国应用自然冷却的范围在逐步扩大。然后针对风侧间接蒸发自然冷却空调系统和水侧间接蒸发自然冷却空调系统的工作原理、模式切换以及运行逻辑进行了分析。按照给出的模式切换点,分别统计全国31个主要城市的系统全年运行时间分布。统计结果表明,在西宁、拉萨、昆明等城市,风侧系统全年不需要开启机械制冷冷源,即可以满足运行要求;在西宁、拉萨、乌鲁木齐等城市,水侧系统全年不需要开启机械制冷冷源,即可以满足运行要求。通过分析指出,随着国际标准和国内标准中对于数据中心的进风状态参数的逐步放宽,风侧间接蒸发自然冷却空调系统和水侧间接蒸发自然冷却空调系统在中国数据中心中具有较大的适用性。This article first based on the latest ASHRAE data center standard to produce China's natural cooling map,which intuitively shows that the scope of China's application of natural cooling is gradually expanding.Then,the working principle,mode switching and operation logic of the air-side indirect evaporative natural cooling air conditioning system and the water-side indirect evaporative natural cooling air conditioning system are analyzed.According to the given mode switching point,the distribution of the annual running time of the system in 31 major cities in China was calculated.The statistical results show that in xining,Lhasa,kunming and other cities,the wind side system does not need to turn on the mechanical cooling source all year round,that is,it can meet the operational requirements.In xining,Lhasa,urumqi and other cities,the water side system does not need to turn on the mechanical cooling source all year round,that is,it can meet the operational requirements.Through analysis,it is pointed out that with the gradual relaxation of the air inlet state parameters in the international standard and the Chinese standard,the indirect evaporative free cooling air conditioning system on the wind side and the indirect evaporative free cooling air conditioning system on the water side have great applicability in the Chinese data center.

关 键 词:数据中心 间接蒸发自然冷却 自然冷却地图 风侧 水侧 统计小时数 

分 类 号:TU83[建筑科学—供热、供燃气、通风及空调工程]

 

参考文献:

正在载入数据...

 

二级参考文献:

正在载入数据...

 

耦合文献:

正在载入数据...

 

引证文献:

正在载入数据...

 

二级引证文献:

正在载入数据...

 

同被引文献:

正在载入数据...

 

相关期刊文献:

正在载入数据...

相关的主题
相关的作者对象
相关的机构对象