检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
作 者:车凯 陈秋 韩忠阁 马宇辉 侯海萍 牛向楠 焦阳 CHE Kai;CHEN Qiu;HAN Zhongge;MA Yuhui;HOU Haiping;NIU Xiangnan;JIAO Yang(State Grid Hebei Electric Power Research Institute,Shijiazhuang 050021,China;State Grid Zhejiang Electric Power Company Jinhua Power Supply Company,Zhejiang Jinhua 321000,China)
机构地区:[1]国网河北省电力有限公司电力科学研究院,石家庄050021 [2]国网浙江省电力有限公司金华供电公司,浙江金华321000
出 处:《高压电器》2021年第12期67-73,共7页High Voltage Apparatus
基 金:国家电网公司科技项目(特高压单柱并联电抗器降噪关键技术深化研究及应用)。
摘 要:以1000kV特高压交流变电站为研究对象,连续3年在工况基本相同条件下对同一变压器、高压电抗器以及场界噪声进行了测量统计,分析了变电站主要设备噪声的分布情况,变化规律与衰减特性。结果表明,连续3年主变压器平均噪声分别为72.9.73.4、74.6 dB(A),平均每年递增0.6 dB(A),通过频谱分析得出主变噪声逐年增加主要由于冷却风扇噪声增加所致。连续3年高压电抗器室内平均噪声分别为77.0、.77.8、79.1 dB(A),平均每年分别递增0.7 dB(A),室外平均噪声分别为65.7、66.7、66.8 dB(A),平均每年分别递增0.4 dB(A),室内外平均噪声相差9.5~14.1 dB(A)。连续3年变电站场界噪声变化规律相近,且站界噪声值较小,变电站内主要设备发出的噪声对周边环境影响甚微。In this paper,the 1000 kV UHV AC substation is taken as an example,the measurement and statistics on the noise of same transformer,HV reactor and filed boundary are performed under the basically identical condition in the consecutive three years.The noise distribution,variation and attenuation feature of the main equipment in the substation are analyzed.The results show that the average noise of main transformer for three consecutive years is 72.9,73.4 and 74.6 dB(A)respectively,with an average increase of 0.6 dB(A)per year.It is concluded through spectrum analysis that the increase of the noise of the main transformer year by year is mainly due to the increase of the noise of the cooling fan.The average noise of the high voltage reactor in the consecutive years is 77.0,77.8 and 79.1 dB(A)respectively,with an average increase of 0.7 dB(A)per year,the average outdoor noise level is 65.7,66.7 and 66.8 dB(A)respectively,with an average increase of 0.4 dB(A)per year and the difference between average indoor and outdoor noise is 9.5〜14.1 dB(A).For three consecutive years,the noise variation of substation field boundary is similar and the noise value in the station boundary is small.The noise from the main equipment in the substation has little impact on the surrounding environment.
关 键 词:1000KV变电站 噪声特性 主变压器 高压电抗器
分 类 号:TM63[电气工程—电力系统及自动化]
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:13.59.210.36