检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
作 者:郑子暄 郑宇 Zheng Zi-xuan;Zheng Yu
机构地区:[1]大连海事大学,辽宁大连116085 [2]天津国能津能滨海热电有限公司,天津300459
出 处:《今日自动化》2021年第11期55-56,共2页Automation Today
摘 要:发电机假同期试验是检验发电机同期装置及其回路正确及完整性的有效手段。常规的假同期试验准备工作繁杂,需进行腾空高压母线等操作,因而具有高耗时性,发电机空载持续长时间运行造成能源的极大浪费。利用邻机同期装置电压采样优化发电机假同期试验方案,既保障了机组安全性又兼顾了机组经济性。Generator false synchronization test is an effective means to check the correctness and integrity of generator synchronization device and its circuit.The preparation of the conventional false synchronization test is complicated,and the high-voltage bus needs to be vacated,so it is timeconsuming.The generator runs without load for a long time,resulting in a great waste of energy.The generator false synchronization test scheme is optimized by using the voltage sampling of adjacent generator synchronization device,which not only ensures the safety of the unit,but also takes into account the economy of the unit.