调压连接方式对暂态传递电压的影响  被引量:2

Effect of Regulating Winding Connection Mode on Transfer Transient Voltage

在线阅读下载全文

作  者:李林达 陈永慈 迟主升 王仁 杨家辉 LI Lin-da;CHEN Yong-ci;CHI Zhu-sheng;WANG Ren;YANG Jia-hui(Siemens Transformer(Guangzhou)Co.,Ltd.,Guangzhou 510530,China;Electric Power Research Institute,CSG,Guangzhou 510663,China)

机构地区:[1]广州西门子变压器有限公司,广东广州510530 [2]南方电网科学研究院,广东广州510663

出  处:《变压器》2021年第12期7-12,共6页Transformer

摘  要:500kV单相自耦中压无载调压的变压器,当调压绕组与低压绕组相邻、中压截波入波时,会在低压到铁心之间感应出很高的冲击传递电压,本文使用波过程仿真的方法,对比了不同的调压连接方式下低压到铁心之间传递电压的变化,进而得出调压的最优连接方案。Regulating winding is adjacent to low voltage winding is a typical winding arrangement for 500 kV single-phase autotransformer with off-circuit tap.During lightning impulse tests,a high impact transfer voltage is induced between the low voltage and the core.In this paper,the wave simulation is used to compare the transfer voltage in key area with different regulated connection modes.The optimal connection scheme is obtained.

关 键 词:500kV单相自耦变压器 绝缘优化 传递电压 调压连接方式 

分 类 号:TM401.1[电气工程—电器]

 