作 者:赵仲勇 陈宇 李阎君 韩孟媛 于跃强 ZHAO Zhong-yong;CHEN Yu;LI Yan-jun;HAN Meng-yuan;YU Yue-qiang(College of Engineering and Technology, Southwest University, Chongqing 400715, China;Bishan Power Supply Branch of State Grid Chongqing Electric Power Company, Chongqing 402760, China)
机构地区:[1]西南大学工程技术学院,重庆400715 [2]国网重庆市电力公司壁山供电分公司,重庆402760
出 处:《科学技术与工程》2021年第36期15469-15475,共7页Science Technology and Engineering
基 金:国家自然科学基金(51807166);重庆市自然科学基金(cstc2019jcyj-msxmX0236)。
摘 要:在电力系统中,串联电抗器常用于限制电网中的短路电流和高次谐波。然而,由于绝缘老化、电压波动、谐波以及外界环境等因素的影响,电抗器会在运行中产生缺陷,严重时会引起烧毁甚至爆炸等事故。其中谐波与温升是引起电抗器绝缘缺陷的重要因素。为提供一种谐波以及温升对10 kV干式铁芯串联电抗器故障的影响的分析思路以便于其运行维护,以一台型号为CKSC-300/10-5的串联电抗器为例,通过建立其等效电路和温度场模型,分析并研究了两种因素对该电抗器烧毁故障的作用效果。结果表明:在选取合适的电抗率下,谐波并不是造成此电抗器烧毁故障的最直接的因素;经过温度场仿真分析,温升也不是造成此电抗器烧毁的直接因素之一,仍需要进一步考虑其他故障原因的影响。In the power system,the series reactor is often used to limit short-circuit current and high-order harmonics in the power grid.However,due to the influence of insulation aging,voltage fluctuation,harmonic and external environment,the reactor produces defects in operation and even cause accidents such as burning or explosion.Among them,harmonic and temperature rise are the important factors causing insulation defects of the reactor.In order to provide an analysis idea of the influence of harmonics and temperature rise on the fault of 10 kV dry-type iron core series reactor for its operation and maintenance,taking a series reactor of CKSC-300/10-5 as an example,through the establishment of its equivalent circuit and temperature field model,the effect of two factors on the burnout fault of the reactor was analyzed and studied.The results show that the harmonic is not the most direct factor to cause the burnout of the reactor under the appropriate reactance rate.The temperature rise is not one of the direct factors to cause the burnout of the reactor through the simulation analysis of the temperature field,and the influence of other fault causes still needs to be further considered.
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:216.73.216.229