一起变电站近区故障导致光差通道中断的事故分析  

An Accident Analysis of Longitudinal Differential Protection Fiber Channel Interruption Because of a Substation Short-line

在线阅读下载全文

作  者:黄岗 王堃 郑植 郑喆 向阳 张星 HUANG Gang;WANG Kun;ZHENG Zhi;Zheng Zhe;XIANG Yang;ZHANG Xing(Zunyi Power Supply Bureau of Guizhou Power Grid Co.,Ltd.,Guizhou Zunyi 563000,China)

机构地区:[1]贵州电网有限责任公司遵义供电局,贵州遵义563000

出  处:《农村电气化》2022年第1期25-26,共2页Rural Electrification

摘  要:分析了一起变电站近区单相接地故障导致2条220 kV线路的8个光差通道同时中断的原因,针对事故原因,提出了完善通信机房内二次接地网等措施,后续事故处理将接地点等电位连接后一点接地,圆满地完成了事故处理,提高了电网的运行可靠性。This article analyzes the reason why 8 fiber channels of two 220 kV lines interrupted at the same time because of a single phase-to-earth fault near the substation.For this improving the secondary grounding grid in communication room is mentioned.Then in following emergency control and restoration all ground points were made into an equal po-tential bonding and grounded at one point.The power grid operation reliability is improved.

关 键 词:变电站近区故障 光差通道 运行可靠性 