作 者:王联合 廖洁娜 宋军 刘章 WANG Lianhe;LIAO Jiena;SONG Jun;LIU Zhang(Quanzhou Power Supply Company,Quanzhou 362000;Nyingchi Power Supply Company,Nyingchi 860000)
机构地区:[1]国网福建省电力有限公司泉州供电公司,福建泉州362000 [2]国网西藏电力有限公司林芝供电公司,西藏林芝860000
出 处:《电力安全技术》2022年第1期23-25,共3页Electric Safety Technology
摘 要:针对一起抗铁磁谐振电压互感器烧毁事件,通过解体互感器检查和分析其内部线圈故障特征,确认故障由10 kV线路误接地引起,并根据其特殊的4PT接线方式原理提出了应对措施,可避免同类设备故障再次发生,也为今后的设备验收和运维新增了又一检查点位。In allusion of an anti-ferroresonance voltage transformer burnt-out event,the damaged transformer is disassembled for checks and analysis,based on which the fault characteristics of its internal coils and the fault cause are confirmed that the burn-out is due to the wrong grounding of a 10 kV line.Countermeasures are put forward based on such a kind of special 4PT wiring mode,which is expected to avoid such a fault once again and add to the check list of equipment acceptance test and maintenance in future.