±500 kV换流站极母线避雷器直流泄漏增大缺陷研究分析  被引量:3

Research and Analysis of Defects of DC Leakage Increasing of Pole Bus Arrester in ± 500 kV Converter Station

在线阅读下载全文

作  者:李威 刘卫东 刘又超 朱传华 卢斌 肖军 吴毅 LI Wei;LIU Weidong;LIU Youchao;ZHU Chuanhua;LU Bin;XIAO Jun;WU Yi(State Grid Hunan Maintenance Company,Changsha 410009,China)

机构地区:[1]国网湖南省电力有限公司检修公司,长沙410009

出  处:《电瓷避雷器》2021年第6期18-24,共7页Insulators and Surge Arresters

摘  要:极母线避雷器是换流站直流输电系统绝缘水平的重要设备,长期运行后的极母线避雷器有概率存在劣化缺陷。本研究对±500 kV鹅城换流站的4组极母线避雷器开展现场直流泄漏试验、拆解后正、反极性试验、并联双柱对比试验、污秽度及憎水性试验,研究结果表明长期运行后的避雷器单元易出现不同程度劣化,直流高压下的极性效应会使正、反向直流试验结果产生偏差,并加速劣化的形成;而避雷器的中上部分有较大概率出现并联柱间偏差,最先形成绝缘薄弱点。The pole bus arrester is an important device for the insulation level of the DC transmission system of the converter station. The pole bus arrester after long-term operation has a possibility of deterioration defects. The author carried out on-site DC leakage test, positive and reverse polarity test after disassembly, parallel double column comparison test, pollution degree and hydrophobicity test for 4 sets of pole bus arresters in ± 500 kV Echeng converter station. The results show that the arrester unit is easy to deteriorate in varying degrees after long-term operation, the polarity effect under DC high voltage will cause the deviation of the forward and reverse DC test results, and accelerate the formation of degradation;and the middle and upper parts of the arrester have a high probability of deviation between parallel columns, the weakest point of insulation is formed first.

关 键 词:极母线避雷器 直流泄漏试验 极性效应 绝缘缺陷 

分 类 号:TM862[电气工程—高电压与绝缘技术]

 

参考文献:

正在载入数据...

 

二级参考文献:

正在载入数据...

 

耦合文献:

正在载入数据...

 

引证文献:

正在载入数据...

 

二级引证文献:

正在载入数据...

 

同被引文献:

正在载入数据...

 

相关期刊文献:

正在载入数据...

相关的主题
相关的作者对象
相关的机构对象