Influence of opening ratios and directions of windows on natural smoke exhaust effect in atrium buildings  被引量:1

在线阅读下载全文

作  者:Peng Wang Xiankun Wang Keheng Chen Hongyu Wei Qianhang Feng Yuanyi Xie Xuechao He Yanqiu Chen 

机构地区:[1]Department of Fire Protection Engineering,Southwest Jiaotong University,Chengdu,Sichuan 610031,China [2]Sichuan Fire Research Institute of MEM,China

出  处:《Building Simulation》2022年第4期571-582,共12页建筑模拟(英文)

基  金:This work was supported by SCFRI research project(No.T2019881101,No.T2019880402).

摘  要:In this paper,the influence of different opening ratios and different opening directions of the windows on the natural smoke exhaust was studied through a series of real fire experiments and simulation analysis.Increasing the open area of the window could effectively improve the overall smoke exhaust effect.When the top windows were open and the opening ratio increased from 19.2%to 24.3%,the optical density was decreased by 12.4%.The average smoke exhaust rate per unit area of the window did not change significantly.Increasing the area of the natural smoke exhaust window could effectively increase the smoke exhaust rate and improve the overall effect of smoke extraction.When the top windows were open,the temperature rise on the top floor was 30.8%-47.5%lower while the visibility was 16.8%-21.9%higher than that when the side windows were open.

关 键 词:natural smoke exhaust ATRIUM opening ratio opening direction 

分 类 号:U492.83[交通运输工程—交通运输规划与管理]

 