From laboratory to on-site operation:Reevaluation of empirically based electric water chiller models  被引量:4

在线阅读下载全文

作  者:Bin Zhang Shijun You Sheng Wang Xiaoxiao Ding Chuang Wang Yan Gao 

机构地区:[1]School of Environmental Science and Engineering,Tianjin University,Tianjin 300072,China [2]State Key Laboratory of Air-Conditioning Equipment and System Energy Conservation,Zhuhai 519070,China [3]Guangdong Key Laboratory of Refrigeration Equipment and Energy Conservation Technology,Zhuhai 519070,China [4]Beijing Key Laboratory of Heating,Gas Supply,Ventilating and Air Conditioning Engineering,Beijing University of Civil Engineering and Architecture,Beijing 100044,China [5]Beijing Advanced Innovation Center for Future Urban Design,Beijing University of Civil Engineering and Architecture,Beijing 100044,China

出  处:《Building Simulation》2022年第2期213-232,共20页建筑模拟(英文)

基  金:supported by the State Key Laboratory of Air-Conditioning Equipment and System Energy Conservation(No.ACSKL2019KT13);National Natural Science Foundation of China(No.51608297 and No.51678024);Scientific Research Project of Beijing Municipal Education Commission(No.KM201910016009 and No.KZ202110016022);Beijing Advanced Innovation Center for Future Urban Design(No.UDC2019011121);Fundamental Research Funds for Beijing University of Civil Engineering and Architecture(No.XI8301).

摘  要:Chiller model is a key factor to building energy simulation and chiller performance prediction.With spread of new types of electric water chillers that have higher performance and wider operating range,new challenges have been faced by building energy simulation tools and their chiller models.This work takes a new type of electric water chiller as a case study and reevaluates eight typical empirically based models for predicting the energy performance of electric water chiller to verify whether they are suitable for the new type of chiller,using both laboratory test data from chiller manufacturer and online monitoring data from on-site operation of a central cooling plant with chillers of the same type.The prediction ability of the chiller models(including model prediction accuracy and generation ability)in laboratory test and on-site operation situations are examined.The results show that the existing models can well describe the chiller performance in the laboratory test situation but perform poorly in the on-site operation situation.As the best two models in the laboratory dataset,the overall prediction errors of DOE-2 and GN model increase more than 250%and 75%respectively in the field dataset.The big discrepancy of model prediction accuracy in the two situations is mainly due to the differences of evaporator and condenser water flow rates between the laboratory and on-site operation datasets,which indicates the limitations of the empirical chiller models and implies further research in future in order to improve the suitability and reliability of chiller model.

关 键 词:electric water chiller performance model model validation model prediction ability variable water flow rates 