检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
作 者:高向宇[1] 史安琪 李杨龙 张国伟[3] 王作杰 李振宇 孟雅 GAO Xiangyu;SHI Anqi;LI Yanglong;ZHANG Guowei;WANG Zuojie;LI Zhenyu;MENG Ya(Beijing Key Laboratory of Earthquake Engineering and Structural Retrofit,Beijing University of Technology,Beijing 100124,China;School of Civil and Transportation Engineering,Beijing University of Civil Engineering and Architecture,Beijing 100044,China;Engineering Structure and New Materials Research Center of Beijing Higher Education Institutions,Beijing University of Civil Engineering and Architecture,Beijing 100044,China)
机构地区:[1]北京工业大学工程抗震与结构诊治北京市重点实验室,北京100124 [2]北京建筑大学土木与交通工程学院,北京100044 [3]北京建筑大学工程结构与新材料北京高等学校工程研究中心,北京100044
出 处:《北京工业大学学报》2022年第7期739-749,共11页Journal of Beijing University of Technology
基 金:北京市自然科学基金资助项目(8141001);国家自然科学基金资助项目(51378038)。
摘 要:为解决钢支撑-钢框排架结构模型计算与试验对比的问题,对该结构体系的动力特性和地震反应进行研究,以某大型电力主厂房结构设计和PKPM计算模型为背景,使用SAP2000软件建立原型结构有限元模型。针对这类具有复杂质量和刚度分布特点的结构体系,提出满足结构动力特性一致性要求的振动台试验物理模型设计原则和相关技术措施,完成缩尺结构模型的构造设计、同条件有限元建模分析及物理模型加工制作.通过振动台试验和有限元模型计算可知,振动台试验模型的前三阶动力特性与有限元模态分析结果基本一致,地震波作用下的试验结构模型动力反应和有限元时程分析的结果可相互印证.结果表明,提出的振动台试验模型设计原则是有效的,试验和计算分析结果可相互印证,可为进一步研究结构抗震性能、改进结构设计提供依据.To solve the problem of comparison between calculation and test of steel braced frame-bent structure model,and to study the dynamic characteristics and seismic response of steel braced frame-bent structure system,the SAP2000 software was used to establish the finite element model of prototype structure and improve the original design based on the structural design and PKPM calculation model of a large electrical power plant.Aiming at the structural system with complex mass and stiffness distribution characteristics,the design principles and relevant technical measures of shaking table test physical model to meet the requirements of structural dynamic characteristics consistency were proposed.The structural design,finite element modeling analysis under the same condition and physical model processing were completed for the scaled structure model.Through the shaking table test of physical model and the time-history analysis of finite element model,the first three order dynamic characteristics of the prototype structure and the shaking table test model were basically consistent with the results of the finite element modal analysis.The dynamic response of the experimental structure model under the action of seismic wave and the time-history analysis results of finite element model were mutually verified.Results show that the design principle of shaking table test model proposed in this paper is effective,and the results of test and calculation analysis can be verified mutually,which can provide a basis for further study of seismic performance of structures and improvement of structural design.
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:216.73.216.49