作 者:童鑫 杨张伟 王雨濛 陶杰 殷忠宁 万欣 TONG Xin;YANG Zhangwei;WANG Yumeng;TAO Jie;YIN Zhongning;WAN Xin(State Grid Anhui Hefei Power Supply Company,Anhui Hefei 230022,China)
出 处:《农村电气化》2022年第8期34-37,共4页Rural Electrification
摘 要:断路器防跳回路主要由若干继电器及辅助节点组成,继电器之间的配合是保证防跳回路和分、合闸回路正确动作的前提。介绍了某变电站母线跳闸事故,并从各方面进行了全面分析,总结出一种断路器防跳回路隐患,确认该隐患为防跳回路中继电器之间在时间上配合不当,导致母线跳闸事故,提出给出了针对该隐患的解决措施。The anti-pumping-circuit of circuit breaker is mainly composed of several relays and auxiliary nodes. The cooperation between relays is the premise to ensure the correct action of the anti-pumping-circuit and the opening and closing circuits. This paper introduces a bus trip accident in a substation, and makes a comprehensive analysis from all aspects, summarizes a hidden danger of the anti-pumping-circuit of circuit breaker, and confirms that the hidden danger is that the relay devices of the anti-pumping-circuit do not cooperate properly in time, resulting in the bus trip accident. Finally, the paper gives the solutions to the hidden danger.