作 者:马瑞刚[1] 崔保群[1] 李爱玲[1] 陈立华[1] 马鹰俊[1] 唐兵[1] 王云峰 黄青华[1] 连钢[1] 柳卫平[1] 武启[2] 王鹏鹏 MA Ruigang;CUI Baoqun;LI Ailing;CHEN Lihua;MA Yingjun;TANG Bing;WANG Yunfeng;HUANG Qinghua;LIAN Gang;LIU Weiping;WU Qi;WANG Pengpeng(China Institute of Atomic Energy,Beijing 102413,China;Institute of Modern Physics,Chinese Academy of Sciences,Lanzhou 730000,China)
机构地区:[1]中国原子能科学研究院,北京102413 [2]中国科学院近代物理研究所,甘肃兰州730000
出 处:《原子能科学技术》2022年第8期1700-1706,共7页Atomic Energy Science and Technology
基 金:国家自然科学基金(11490560);中核集团公司集中研发项目(FA18000201)。
摘 要:本文介绍了锦屏深地强流高压加速器自动控制系统的基本结构、控制软件和安全联锁设计,阐述了该加速器在运行过程中高压打火产生的强干扰影响控制系统和相关设备的正常运行及在调试和实验过程中遇到的问题。通过分析原因,采取各种保护措施提高控制系统的抗干扰能力,确保控制系统和设备运行的稳定性。Nuclear astrophysics is an interdisciplinary research field that integrates nuclear physics and astrophysics.The ultimate goal of nuclear astrophysics is to understand how nuclear processes generate the energy of stars over their lifetimes and,in doing so,synthesize heavier elements from the primordial hydrogen and helium in the big bang which lead to the expanding universe.It mainly aims at study of the origin of elements and how nuclear processes affect the evolution and fate of stars in the universe.In order to meet the need of the nuclear astrophysics experiment,a low energy,high stability,high-current and high-voltage accelerator was required to carry out the related nuclear astrophysics experiments by direct measurement method under the ultra-low background environments.A high-current and high-voltage accelerator was developed by China Institute of Atomic Energy and Institute of Modern Physics for the underground laboratory of Jinping Mountain.The hardware structure of the accelerator control system adopted the distributed control system based on PLC.The PROFIBUS field bus was used to realize data exchange between the main frame and extended frame in PLC control system.Industrial ethernet was used for data communication between the field control layer and the operation layer.The control system software adopted the distributed control framework based on EPICS clients/server mode,which is composed of interface module OPI for clients,input/output control module IOC for server and channel access module CA.The operation monitoring software with the interactive control interface was developed with EPICS configuration software.There are main control window,vaccum system window,safety interlock setting window,and ion source windows.The parameters of accelerator can be set and displayed easily.The combination of hardware and software protection was adopted to ensure the accelerator’s reliability.A complete safety interlock system was installed to ensure the safety of equipment and personnel.The problem of strong i
分 类 号:TL503.6[核科学技术—核技术及应用]
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:216.73.216.7