基于组合激光光源的双组分微量气体检测系统  被引量:3

Two-component trace gas detection system based on combined laser light sources

在线阅读下载全文

作  者:朱文江 余银辉 李辰溪 安冉 陈珂 ZHU Wenjiang;YU Yinhui;LI Chenxi;AN Ran;CHEN Ke(China General Nuclear Power Group,Shenzhen 518100,China;School of Optoelectronic Engineering and Instrumentation Science,Dalian University of Technology,Dalian 116024,China)

机构地区:[1]中广核研究院有限公司,深圳518100 [2]大连理工大学光电工程与仪器科学学院,大连116024

出  处:《激光技术》2022年第5期657-662,共6页Laser Technology

基  金:国家自然科学基金资助项目(61905034)。

摘  要:CH_(4)和C_(2)H_(2)是变压器发生故障时两种重要的特征气体。为了实现对变压器中溶解的微量CH_(4)和C_(2)H_(2)气体含量检测的需求,采用激光光声光谱气体检测技术,通过分析CH_(4)和C_(2)H_(2)气体的近红外吸收谱线,选取合适的激光光源并确定激光调制参数;设计并搭建了一套以双激光光源和非共振光声池为核心的光声光谱微量CH_(4)和C_(2)H_(2)气体检测系统,获得了系统对CH_(4)和C_(2)H_(2)气体检测灵敏度和低含量检测误差。结果表明,CH_(4)和C_(2)H_(2)气体分别在体积分数为0~1000×10^(-6)和0~500×10^(-6)的范围内具有良好的线性响应,每10^(-6)体积分数的检测响应度分别为5.8969μV和16.1831μV;在低含量CH_(4)/C_(2)H_(2)混合气体对系统的重复性和精度测试中,CH_(4)气体体积分数为3.00×10^(-6)时的检测最大绝对误差为0.30×10^(-6),C_(2)H_(2)气体体积分数为0.50×10^(-6)时的检测最大绝对误差为0.20×10^(-6)。此研究结果满足测量误差的技术指标要求,实现了对微量CH_(4)和C_(2)H_(2)气体的高灵敏度检测。Methane and acetylene are the most important characteristic gases when the transformer breaks down.In order to meet the demand for detecting the concentration of the trace CH_(4)and C_(2)H_(2)dissolved in the transformer,the laser photoacoustic spectroscopy gas detection technology was adopted.By analyzing the near-infrared absorption spectrum of CH_(4)and C_(2)H_(2)gas,the appropriate laser light source was selected and the laser modulation parameters were determined.A set of photoacoustic spectroscopy trace CH_(4)and C_(2)H_(2)gas detection system with dual laser light source and a non-resonant photoacoustic cell were designed,and the detection sensitivity and low concentration detection error of the system for CH_(4)and C_(2)H_(2)gas was obtained.The result shows that CH_(4)and C_(2)H_(2)have good response linearity in the volume fraction range of 0~1000×10^(-6)and 0~500×10^(-6),respectively,and the responsivities are 5.8969μV and 16.1831μV per 10^(-6)volume fraction,respectively.The system is tested for repeatability and accuracy using low-content CH_(4)/C_(2)H_(2)mixed gas.The maximum absolute error of detection is 0.30×10^(-6)when the CH_(4)volume fraction is 3.00×10^(-6),and the maximum absolute error of detection is 0.20×10^(-6)when the C_(2)H_(2)volume fraction of 0.50×10^(-6).The research results meet the technical index requirements of measurement error and achieve high-sensitivity detection of trace CH_(4)and C_(2)H_(2).

关 键 词:测量与计量 油中溶解气体分析 光声光谱 变压器 

分 类 号:O433.4[机械工程—光学工程]

 

参考文献:

正在载入数据...

 

二级参考文献:

正在载入数据...

 

耦合文献:

正在载入数据...

 

引证文献:

正在载入数据...

 

二级引证文献:

正在载入数据...

 

同被引文献:

正在载入数据...

 

相关期刊文献:

正在载入数据...

相关的主题
相关的作者对象
相关的机构对象