数字化变电站远动装置通信异常分析与改进  

Analysis and Improvement of Communication Abnormality of Telecontrol Device in Digital Substation

在线阅读下载全文

作  者:李文明 李国杰 马盟军 LI Wenming;LI Guojie;MA Mengjun(Xuji Electric Co.,Ltd.,Xuchang 461000,China)

机构地区:[1]许继电气股份有限公司,河南许昌461000

出  处:《电工技术》2022年第18期101-103,共3页Electric Engineering

摘  要:通过对三个数字化变电站中远动装置与间隔层装置通信异常问题的分析,得出通信异常原因:一是远动装置与间隔层装置通信策略有缺陷;二是connect{}函数不应使用阻塞模式;三是BCM芯片的默认配置模式设置不当。通过针对性的设计优化、完善,消除了设计缺陷,提高了远动装置通信的可靠性。By analyzing the abnormal communication between the telecontrol device and the bay device in three digital substations,the reasons for the abnormal communication are obtained.Firstly,the communication coordination strategy between the telecontrol device and the bay device is defective.Secondly,the connect{}function should not use blocking mode.Thirdly,the default configuration mode of BCM chip is improper.Through targeted design optimization and improvement,the design defects are eliminated,the communication reliability of telecontrol device is improved.

关 键 词:远动装置 间隔层装置 通信 阻塞模式 网络风暴 

分 类 号:TM732[电气工程—电力系统及自动化]

 