作 者:牟大林 林圣[1] 李小鹏 戴文睿 MU Dalin;LIN Sheng;LI Xiaopeng;DAI Wenrui(School of Electric Engineering,Southwest Jiaotong University,Chengdu 610031,China;State Grid Sichuan Electric Power Research Institute,Chengdu 610041,China;Standards and Metrology Research Institute,China Academy of Railway Sciences Corporation Limited,Beijing 100081,China)
机构地区:[1]西南交通大学电气工程学院,四川成都610031 [2]国网四川省电力公司电力科学研究院,四川成都610041 [3]中国铁道科学研究院集团有限公司标准计量研究所,北京100081
出 处:《电力系统保护与控制》2022年第21期88-98,共11页Power System Protection and Control
基 金:国家自然科学基金项目资助(51977183)。
摘 要:为探究现有直流输电线路行波保护对白鹤滩-江苏特高压混合直流输电系统(简称:白江混合系统)的适应性,根据白江混合系统直流线路故障附加网络推导直流线路区内外故障时线路两端故障行波的边界传播特性。分析发现,直流线路正向区外故障后边界传播特性与传统直流系统存在差异。进一步分析行波保护判据的变化情况,表明行波保护判据主要受整流侧反射系数和逆变侧折射系数的影响。将白江混合系统与传统直流输电系统进行对比,发现当直流输电线路正向区外发生短路故障后,白江混合系统电压变化量、电压变化率、极波变化量和极波变化率比传统直流系统变化更大,导致行波保护误动风险增大。最后,基于PSCAD搭建白江混合系统仿真模型,仿真结果验证了理论分析的正确性。To explore the adaptability of existing traveling wave protection for the DC line to Baihetan-Jiangsu serial hybrid ultra-high voltage direct current(UHVDC)transmission system(Bai-Jiang hybrid system for short),this paper deduces the boundary propagation characteristics of the fault traveling wave at both ends of the DC line during faults inside and outside the DC line zone based on the fault additional network of the Bai-Jiang hybrid system.The analysis finds that the boundary propagation characteristics of the forward zone of the DC line faults differ from those of the conventional line commutated converter(LCC)HVDC system.The changes for the traveling wave protection criterion are analyzed,and this analysis shows that the traveling wave protection criterion is mainly affected by the reflection coefficient on the rectifier side and the refraction coefficient on the inverter side.Comparing the Bai-Jiang hybrid system with a conventional LCC-HVDC system,it is found that when a short-circuit fault occurs outside the forward zone of the DC line,the voltage change amount and change rate,the polar wave change amount and change rate of the Bai-Jiang hybrid system change more than those of the conventional LCC-HVDC system.That leads to an increased risk of false operation of the traveling wave protection.Finally,a simulation model of the Bai-Jiang hybrid system is built based on PSCAD,and the results verify the correctness of the theoretical analysis.
关 键 词:混合直流输电系统 直流输电线路 行波保护 适应性分析 边界传播特性
分 类 号:TM721.1[电气工程—电力系统及自动化]
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:216.73.216.15