1000 MW锅炉火检冷却风源系统改造  被引量:1

Retrofit of the Cooling Air Source System for Flame Detection in a 1000 MW Boiler

在线阅读下载全文

作  者:徐育伟 Xu Yuwei(SPIC&GCL Binhai Electric Power Generation Co.,Ltd.,Yancheng 224500,Jiangsu Province,China)

机构地区:[1]国家电投集团协鑫滨海发电有限公司,江苏盐城224500

出  处:《发电设备》2022年第6期437-440,共4页Power Equipment

摘  要:某电厂1000 MW锅炉火检冷却风量小,火检探头在高温运行下容易出现结焦或烧损的问题,通过从冷一次风源母管引入冷却风来替代原火检冷却风源,使原火检冷却风机停机备用。改造后的系统可以保证锅炉的正常运行,同时可以节约费用。For a 1 000 MW boiler in a power plant, the coking and burning damage of the flame detector probe occurs easily during high temperature operation, which is caused by the small flow rate of the cooling air for flame detection. To solve this problem, the cooling air form the existing air source system for flame detection was replaced by from the main piping of the cooling primary air source, while the existing fans of the cooling air for the flame detection shut down for standby. The retrofitted system can ensure the normal operation of the boiler and save the cost.

关 键 词:锅炉 火检冷却风 风机 冷一次风 风源系统 

分 类 号:TM621.7[电气工程—电力系统及自动化]

 