非典型110kV电缆瓷套终端发热漏油缺陷分析  

Analysis for Heating and Oil-leakage Defect of 110kV Cable Porcelain Bushing Terminal

在线阅读下载全文

作  者:全万霖 李定宁 孔诗琦 张珏 慕容啟华 单鲁平 QUAN Wanlin;LI Dingning;KONG Shiqi;ZHANG Jue;MURONG Qihua;SHAN Luping(Guangzhou Power Supply Bureau Co.,Ltd.,Guangzhou 510665,China)

机构地区:[1]广东电网有限责任公司广州供电局,广东广州510665

出  处:《电工技术》2022年第19期73-76,79,共5页Electric Engineering

摘  要:典型输电电缆瓷套终端尾管发热多为局部发热,在红外测温图片中表征为集中高亮度热点。针对某110 kV电缆瓷套终端红外测温中发现的尾管直至底座整体发热异常进行了分析,结合终端结构及后续现场抢修过程中发现的该组终端漏油情况,对此类整体发热特征缺陷的形成机理进行了探讨,指出该类终端结构上存在的问题及工艺上可能的诱因,并从结构和工艺上提出了相应的建议。研究结果可为高压输电电缆运维工作提供参考。The typical heating of transmission cable porcelain bushing terminal is mostly local,which is characterized as concentrated high brightness hot spot in infrared temperature measurement photos.In this paper,the abnormal heating of the tail pipe to the base found in the infrared temperature measurement of the porcelain bushing terminal of a 110 kV cable is analyzed.Combined with the terminal structure and the oil leakage of this group of terminals found in the follow-up on-site repair process,the formation mechanism of this kind of overall heating characteristic defect is discussed,and the problems existing in this kind of terminal structure and possible inducements in technology are pointed out.The problems existing in the structure of this kind of terminal and the possible inducements in technology are pointed out,and corresponding suggestions from the structure and technology is put forward.

关 键 词:电缆终端 瓷套 发热 漏油 红外测温 

分 类 号:TM755[电气工程—电力系统及自动化]

 