摘  要:结合某核电站3、4号机调试期间主泵电机保护异常跳闸现象,对故障原因进行了分析,发现这是零序电流互感器的安装位置选择不合适,产生的较大零序电流使得零序保护无法躲过导致的,并提出了解决办法,为以后相关调试工作积累了丰富经验。During the commissioning of unit 3 and unit 4 of a nuclear power station,the motor protection of the main pump tripped abnormally.The cause of the fault is analyzed,and it is found that the installation position of the zero-sequence current transformer is not suitable,and the large zero-sequence current generated makes the zero-sequence protection unable to escape.The solutions are put forward,which accumulated rich experience for relevant commissioning work in the future.