基于夹点理论的人工冰场CO_(2)制冷热回收系统优化分析  被引量:2

Optimization Analysis of CO_(2)Refrigeration and Heat Recovery System for Ice Rink Based on Pinch Point Theory

在线阅读下载全文

作  者:周啸虎 耿旭东 李锋 司春强 马进 邵双全 Zhou Xiaohu;Geng Xudong;Li Feng;Si Chunqiang;Ma Jin;Shao Shuangquan(School of Energy and Power Engineering,Huazhong University of Science and Technology,Wuhan,430074,China;Huashang International Engineering Co.,Ltd.,Beijing,100069,China)

机构地区:[1]华中科技大学能源与动力工程学院,武汉430074 [2]华商国际工程有限公司,北京100069

出  处:《制冷学报》2022年第6期57-64,共8页Journal of Refrigeration

基  金:国家重点研发计划(2019YFF0301504);国家自然科学基金(52076085)资助项目。

摘  要:在碳中和背景下,天然工质CO_(2)在制冷及制热应用中受到日益广泛的关注。本文采用夹点分析理论,对人工冰场的CO_(2)制冷及热回收系统中双级热回收结构进行了优化分析。在假设两级串联热回收(低温热回收进出口水温为40℃和60℃,高温级进出口水温为60℃和80℃)的情况下,通过改变某一级的水质量流量,得到以下分析结果:夹点的存在会升高热回收换热器的CO_(2)出口温度,降低系统的热回收量、制热性能系数以及综合COP,同时对应于最大COP的最佳排气压力也会后移,直至超出上限(当第二级质量流量比为0.4时,可通过调节第一级质量流量比来消除夹点的影响;而第一级质量流量比为0.4时,最佳排气压力由10.2 MPa升至10.9 MPa,同时最大综合COP由3.538降至2.843);为尽量提升系统性能,应在合理范围内,降低第二级水质量流量,提高第一级水质量流量,同时提高排气压力。Against the backdrop of carbon neutralization,CO_(2) has attracted increasing attention as a natural working medium for refrigeration and heating applications.Based on pinch point analysis,a CO_(2) refrigeration and heat recovery system for an ice rink is optimized and analyzed.Under the assumption of two-stage heat recovery(water temperatures at the inlet and outlet are 40℃and 60℃for low-temperature heat recovery and 60℃and 80℃for high-temperature heat recovery),the following results were obtained by changing the water mass flow rate at a specific stage.The existence of the pinch point increased the CO_(2) outlet temperature for heat recovery in the heat exchanger and reduced the amount of recovered heat,heating coefficient of performance(COP_(hr)),and comprehensive COP of the system.The optimal discharge pressure corresponding to the maximum COP also increased until it exceeded the upper limit.When the mass flow ratio of the second stage is 0.4,the influence of the pinch point can be eliminated by adjusting the mass flow ratio of the first stage.When the mass flow ratio of the first stage is 0.4,the optimal discharge pressure increased from 10.2 MPa to 10.9 MPa,while the maximum comprehensive COP decreased from 3.538 to 2.843.To improve the system performance,the mass flow rate of water at the second and first stages should be decreased and increased,respectively,while the discharge pressure should be increased within a reasonable range.

关 键 词:人工冰场 制冷热回收系统 夹点分析 CO_(2) 性能系数 

分 类 号:TB611[一般工业技术—制冷工程] TB69

 

参考文献:

正在载入数据...

 

二级参考文献:

正在载入数据...

 

耦合文献:

正在载入数据...

 

引证文献:

正在载入数据...

 

二级引证文献:

正在载入数据...

 

同被引文献:

正在载入数据...

 

相关期刊文献:

正在载入数据...

相关的主题
相关的作者对象
相关的机构对象