检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
作 者:周觅路 鲁林军 ZHOU Milu;LU Linjun(Nanning Power Supply Bureau of Guangxi Power Grid Co.,Ltd.,Guangxi Nanning 530022,China;Guangxi Power Grid Co.,Ltd..Guangxi Nanning 530000,China)
机构地区:[1]广西电网有限责任公司南宁供电局,广西南宁530022 [2]广西电网有限责任公司,广西南宁530000
出 处:《广西电力》2022年第3期62-68,共7页Guangxi Electric Power
摘 要:供电可靠性是指配电网向用户持续供电的能力,是对电力用户服务水平的综合体现。本文总结了某供电局在电网转供电能力支撑不足的情况下,实现用户负荷全部或者部分转移的常用解决办法,详细介绍了一座110 kV变电站全停时面临的困难和解决思路,通过合环转供电、站内并接出线、穿越母线等转供电技术的应用减少客户平均停电时间0.65小时/户,在中西部供地区具备广泛的推广价值。Power supply reliability is the capability of distribution network to continuously supply power to customers, which is a comprehensive indicator of the power service quality. This paper summarizes the common methods for a power supply bureaus to realize complete or incomplete load transfer when the power grid transfer capacity is insufficient. The difficulties and solutions faced when a 110kV substation is completely shut down are introduced in detail, and the average interruption hour of customer can be reduced by 0.65hours/household through application of power supply transfer techniques such as closing the loop, connecting outlet lines in the station,and crossing the busbar and so on. These solutions have extensive promotion prospects in the central and western regions in China.
关 键 词:供电可靠性 转供电 供电能力 穿越母线 客户平均停电时间
分 类 号:TM72[电气工程—电力系统及自动化]