作 者:何必伦 曹炜 卫皇莅 桂世成 王超 HE Bilun;CAO Wei;WEI Huangli;GUI Shicheng;WANG Chao(Electric Power Engineering of Shanghai University of Electric Power,Shanghai 200090,China)
出 处:《电力科学与技术学报》2022年第6期150-156,197,共8页Journal of Electric Power Science And Technology
基 金:国家自然科学基金青年基金(51807114);上海电力公司技术咨询项目(SGSHJY00GPJS1900054)。
摘 要:目前在电网扩建规划仿真中,新规划元件零序参数的取值范围比较宽泛,具体取值缺乏依据,影响单相短路电流计算结果的可信性。为此,提出一种基于PSD-BPA平台用于电网扩建规划的零序参数取值方法,以某地方电网各个分区为典型场景,分析典型场景中BPA暂态稳定程序中500 kV主变零序参数XO卡、220 kV线路零序参数LO卡、220 kV主变高压侧母线下级等值零序参数XR卡值的变动对500 kV变电站220 kV侧母线单相短路电流的影响;通过误差分析找出关键影响因素,再按照计算误差的要求,抓住主要忽略次要,给出对应零序卡的取值方法建议。实例分析表明:所提方法能够便捷、有效地评估规划年某地方电网500 kV变电站220 kV侧母线单相短路电流,可应用于工程实际。At present,when planning the expansion of power grids,the range of zero-sequence parameter of the new planning equipment is relatively wide and lacks references,which affects the credibility of the result of single-phase short-circuit current.Thus,a zero-order parameter selection method based on the PSD-BPA platform for power grid expansion planning is proposed.Taking each partition of a local power grid as a typical scenario,the influence of the changes of zero sequence parameter XO card of 500 kV main transformer,zero sequence parameter LO card of 220 kV line,and sub equivalent zero sequence parameter XR card value of high-voltage side bus of 220 kV main transformer on single-phase short-circuit current of 220 kV side bus in that scenario of the BPA transient stability are analyzed.The key influencing factors are identified through error analysis,then according to the requirements of the calculation error,give advices to zero sequence of accessor according to the included important factors.An example analysis shows that the proposed method can easily and effectively evaluate the single-phase short-circuit current of bus at 220 kV side of Shanghai power grid 500 kV substation in the planning year,and can be applied to engineering practice.
关 键 词:单相短路 零序参数 灵敏度 电网规划 PSD-BPA
分 类 号:TM713[电气工程—电力系统及自动化]
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:216.73.216.49