检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
作 者:周春[1] 汪玲玲[1] 张前 ZHOU Chun;WANG Lingling;ZHANG Qian
机构地区:[1]中机国际工程设计研究院有限责任公司华东分院,江苏南京210023
出 处:《煤气与热力》2023年第1期V0026-V0029,共4页Gas & Heat
摘 要:根据现行规范,燃气供应站LPG或LNG储罐固定水喷雾系统中供水控制阀应选用雨淋报警阀,并配置雨淋报警阀组。气动控制阀的开关时间能做到5 s以内,与雨淋报警阀的动作时间相近。实际应用中,以气动控制阀作为供水控制阀的固定水喷雾系统响应时间能够做到小于120 s。气动控制阀作为燃气供应站LPG或LNG储罐固定水喷雾系统供水控制阀是可行的。According to the current specifications,the water supply control valve in the fixed water spray system of LPG or LNG storage tank in the gas supply station shall be deluge alarm valve and equipped with deluge alarm valve group.The opening and closing time of the pneumatic control valve can be within 5 s,which is similar to the action time of the deluge alarm valve.In practical application,the response time of the fixed water spray system with the pneumatic control valve as the water supply control valve can be less than 120 s.It is feasible to use pneumatic control valve as water supply control valve for fixed water spray system of LPG or LNG storage tank in gas supply station.
关 键 词:燃气供应站 供水控制阀 雨淋报警阀 气动控制阀 固定水喷雾系统
分 类 号:TU996.6[建筑科学—供热、供燃气、通风及空调工程]