检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
作 者:陈凌 龙震泽 邓斌 罗华东 廖强[2] 丁玉栋[2] CHEN Ling;LONG Zhenze;DENG Bin;LUO Huadong;LIAO Qiang;DING Yudong(State Grid Sichuan Electric Power Research Institute,Chengdu 610094,China;Institute of Engineering Thermophysics,Chongqing University,Chongqing 400030,China)
机构地区:[1]国网四川省电力公司电力科学研究院,四川成都610094 [2]重庆大学工程热物理研究所,重庆400030
出 处:《热科学与技术》2022年第6期595-601,共7页Journal of Thermal Science and Technology
基 金:国家电网有限公司科技项目资助项目(52199718001R).
摘 要:利用田口法对具有不同肋结构参数的竖直三维内肋管管内变压器油自然对流换热特性进行了实验研究,获得了肋高、肋宽、轴向间距和周向间距等肋结构参数对管内自然对流换热性能的影响规律,提出了肋结构参数最佳组合。结果表明:变压器顶层油温从40变化至100℃,肋高和肋宽对换热性能的影响占比基本不变,周向间距的影响占比逐渐减小,轴向间距的影响占比逐渐增大;相比光管,三维内肋管的自然对流强化换热性能随顶层油温的增大而增加,变压器油自然对流Nu最大约为光管的1.75倍。拟合了竖直三维内肋管管内变压器油自然对流换热计算关联式,其与实验数据的最大偏差为±16%。The natural-convection heat transfer characteristics of transformer oil inside the three-dimensional(3-D)internally finned tubes were experimental investigated by using Taguchi method.The effects of fin structural parameters(fin height,fin width,axial fin pitch and circumferential fin pitch)on the performance of transformer oil nature-convection heat transfer in 3-D internally finned tubes were presented,and the optimum combination of fin structural parameters was put forward.The results show that when the top oil temperature of transformer varied from 40 to 100℃,the influence of fin height and fin width on the heat transfer performance was barely changed,however the influence of circumferential fin pitch decreased gradually,and the influence of axial fin pitch increased gradually.Compared with that of smooth tube,the nature-convection heat transfer augmentation of 3-D internally finned tube was increasingly apparent with the increasing of top oil temperature of transformer,and the maximum Nusselt(Nu)number was approximately 1.75 times bigger than that of smooth tube in the scope of experiments.Finally,the empirical correlation of transformer oil nature-convection heat transfer was proposed for vertical 3-D internally finned tube,the predicted values of Nu number in agreement with the experimental values within the error of±16%.
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:3.144.100.3