高压XLPE电缆缓冲层烧蚀故障原因与检测关键技术  被引量:4

Analysis Ablation Failure Causes on Buffer Layer of High Voltage XLPE Cable and Key Detection Technologies

在线阅读下载全文

作  者:周韫捷 李海 范玉军 代娜 ZHOU Yunjie;LI Hai;FAN Yujun;DAI Na(State Grid Shanghai Cable Company,Shanghai 200072,China;Shanghai National Center of Testing and Inspection for Electric Cable and Wire Co.,Ltd.,Shanghai 200444,China)

机构地区:[1]国网上海市电力公司电缆分公司,上海200072 [2]上海国缆检测股份有限公司,上海200444

出  处:《电线电缆》2023年第1期26-29,共4页Wire & Cable

基  金:国家电网有限公司总部管理科技项目资助(5200-201917070A-0-0-00)。

摘  要:高压交联聚乙烯(XLPE)电缆的缓冲层因烧蚀而导致的线路故障已多次出现,其原因尚无定论。为了探究烧蚀故障的原因,从电缆阻水带缓冲层角度出发,分析了阻水带缓冲层含水率、电缆阻水类型和阻水带缓冲层电性能等因素对烧蚀故障的影响。结果表明:在电缆安装或正式使用之前,对阻水带缓冲层含水率、体积电阻、表面电阻和成品电缆缓冲层接触电阻率等方面进行检测,可减少或避免电缆缓冲层烧蚀故障的发生。The lines fault caused by ablation of the buffer layer of high voltage cross linked polyethylene(XLPE)cable has occurred many times, and the reason why the defects occurred is still inconclusive. In order to explore the causes of ablation failure, from the perspective of cable water stop buffer layer, the effects of water content of water stop buffer layer, cable water stop type and electrical performance of water stop buffer layer on ablation failure were analyzed. The results showed that in order to reduce or avoid the ablation failure of cable buffer layer, four aspects of water content, volume resistance, surface resistance and contact resistance of finished cable buffer layer must be tested before cable installation or formal use.

关 键 词:高压交联聚乙烯电缆 缓冲层 烧蚀 故障原因 检测技术 