输电线路架空地线悬垂线夹承重轴磨损原因分析及对策  被引量:2

Cause Analysis and Countermeasures for Wearing of Load-Bearing Shaft of Suspension Clamp for Overhead Ground Wire of Transmission Line

在线阅读下载全文

作  者:鲍明正 祝永坤 吴昊 杨志超 于开文 BAO Mingzheng;ZHU Yongkun;WU Hao;YANG Zhichao;YU Kaiwen(State Grid Inner Mongolia Eastern Electric Power Co.,Ltd.,Hohhot 010010,China)

机构地区:[1]国网内蒙古东部电力有限公司,呼和浩特010010

出  处:《内蒙古电力技术》2022年第6期46-50,共5页Inner Mongolia Electric Power

摘  要:针对某±500 kV直流输电线路架空地线悬垂线夹承重轴断裂的问题,结合该线路设计条件及平断面定位图、地形地貌、气象条件等,通过地线悬垂线夹外观、尺寸检查以及金相、硬度检测,对悬垂线夹受力情况进行了全面分析,认为造成地线悬垂线夹承重轴断裂的原因主要为档距比大、风力影响、地形地貌复杂等,并从技术和运维管理方面提出了优化档距、采用耐磨金具等处理建议及防范措施。In view of the breakage of the load-bearing shaft of a±500 kV DC transmission line overhead ground wire clamp,combined with the design conditions of the line and the plane cross section diagram,topography and geomorphology,meteorological conditions,etc,through the appearance and size inspection of the ground wire suspension clamp,as well as metallographic and hardness testing,this paper comprehensively analyzes the stress of the suspension clamp,and concludes that the main causes of the load-bearing shaft fracture are large gear ratio,wind influence,complex topography and geomorphology,etc.From the aspects of technology and operation and maintenance management,treatment suggestions and preventive measures such as optimizing the gear span and using wear-resistant hardware.

关 键 词:输电线路 架空地线 风荷载 悬垂线夹 承重轴 磨损 

分 类 号:TM75[电气工程—电力系统及自动化]

 