检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
作 者:崔胜涛 Cui Shengtao(Xinjiang Oil and Gas Transportation Branch of State Pipe Network Group Western Pipeline Co.,Ltd.,Urumqi,830000,China)
机构地区:[1]国家管网集团西部管道有限责任公司新疆输油气分公司,乌鲁木齐830000
出 处:《仪器仪表用户》2023年第3期26-29,共4页Instrumentation
摘 要:西气东输一线RR压缩机组控制系统设备使用年限较为长久,控制器的冗余切换故障问题出现较为频繁,严重影响压缩机的平稳运行。本文主要以解决RR压缩机控制系统冗余切换问题为目的,通过机组控制程序分析、报警信息分析、系统运行状态诊断、系统网络优化、功能测试及资料查阅等方法,分析压缩机组冗余切换故障发生的原因,制定了控制网的优化、看门狗时间优化,对外通信连接数精减,对外通信连接路径优化,故障模块更换等优化措施,从而提升压缩机组平稳运行的可靠性。The control system equipment of RR compressor unit in the first line of West East Gas Pipeline has been used for a long time, and the redundancy switching failure of controller occurs frequently, which seriously affects the smooth operation of compressor. The purpose of this paper is to solve the redundancy switching problem of RR compressor control system. By means of unit control program analysis, alarm information analysis, system operation status diagnosis, system network optimization, function test and data review, the causes of compressor unit redundancy switching failure are analyzed. The optimization of control network,watchdog time, external communication connection number reduction, external communication connection path optimization Replacement of faulty modules and other optimization measures to improve the reliability of smooth operation of the compressor unit.
关 键 词:RR压缩机组 看门狗时间 CPU使用率 冗余切换 网络优化
分 类 号:TH45[机械工程—机械制造及自动化] TP273[自动化与计算机技术—检测技术与自动化装置]