间接蒸发冷却技术在北京地区数据中心的应用分析  被引量:4

Application Analysis of Indirect Evaporative Cooling Technology in Beijing Data Center

在线阅读下载全文

作  者:颜晓光[1] Yan Xiaoguang(Beijing Shougang International Engineering Technology Co.,Beijing,100041)

机构地区:[1]北京首钢国际工程技术有限公司,北京100041

出  处:《制冷与空调(四川)》2023年第1期115-123,共9页Refrigeration and Air Conditioning

摘  要:结合北京地区的气候特点,分析了间接蒸发冷却空调在数据中心不同送/回风温度、冷却效率时的切换温度及全年运行时长;通过建立计算模型,计算了对应不同空调送/回风温度、间接冷却效率时的能耗情况,并以某数据中心为例,计算了采用间接蒸发冷却空调和传统空调的初投资、运行费用等;根据计算结果分析,同等冷却效率下,提高空调送回风温度可显著降低全年空调电耗;采用间接蒸发冷却空调比传统空调节省电耗44%。Combined with the climatic characteristics of Beijing, this paper analyzes the switching temperature and annual operating time of indirect evaporative cooling air conditioners in the data center with different supply/return air temperatures,cooling efficiency;By establishing a calculation model, the energy consumption corresponding to different air-conditioning supply/return air temperatures and indirect cooling efficiency was calculated. Taking a data center as an example, the initial investment and operating costs of indirect evaporative cooling air conditioners and traditional air conditioners were calculated;According to the analysis of the calculation results, under the same cooling efficiency, increasing the temperature of the air-conditioning supply and return air can significantly reduce the annual power consumption of the air-conditioning;the use of indirect evaporative cooling air-conditioning saves 45% of the power consumption compared with the traditional air-conditioning.

关 键 词:间接蒸发冷却 间接蒸发冷却效率 切换温度 电耗 初投资 静态投资回收期 

分 类 号:TU834[建筑科学—供热、供燃气、通风及空调工程]

 

参考文献:

正在载入数据...

 

二级参考文献:

正在载入数据...

 

耦合文献:

正在载入数据...

 

引证文献:

正在载入数据...

 

二级引证文献:

正在载入数据...

 

同被引文献:

正在载入数据...

 

相关期刊文献:

正在载入数据...

相关的主题
相关的作者对象
相关的机构对象