摘 要:针对65 MW发电机组2000 kW变频传动给水泵运行差流过大,差动电流保护无法投入运行的现象,从保护原理上进行分析,发现原设计的保护设备配置存在错误。通过改变电流互感器的安装位置,更改二次接线,实现了一次、二次设备相序与相位的正确匹配,消除了差流,达到了安全运行要求。For 2000 kW variable frequency driving feed water pump of 65 MW generator to run through the large,the phenomenon of differential current protection cannot be put into operation,were analyzed from the protection principle,found that the original design of the protection device configuration errors,by changing the installation position of current transformer,secondary wiring changes,phase sequence of primary and secondary equipments can be realized with the correct phase matching,The differential flow is eliminated and the safe operation is achieved.