检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
作 者:刘伟 LIU Wei(Shenneng Ansuogu(Ghana)Electric Power Co.,Ltd.,Shenzhen 518000,China)
机构地区:[1]深能安所固(加纳)电力有限公司,广东深圳518000
出 处:《电工技术》2023年第2期11-13,共3页Electric Engineering
摘 要:按照《防止电力生产安全重大事故的二十五项重点要求》,电力企业应设置主汽温度10 min内下降超50℃跳机保护,但是目前国内多数PG9171E型联合循环机组均未设置该保护。介绍了某厂Symphony Plus S+系统用多种方式搭建该保护,且对搭建过程和应用环境进行了阐述,为其他电厂Symphony Plus S+系统实现该功能提供参考和借鉴。According to the"Twenty-five key requirements for preventing major accidents in power production safety",power companies should set up the trip protection when the temperature of the main steam turbine drops over 50℃ within 10min.The case of a factory’s Symphony Plus S+system building this protection in a variety of ways is introduced,and the construction process and application environment are explained.This paper provides reference for other power plants to implement this function in the Symphony Plus S+system.
关 键 词:Symphony Plus S+ 汽轮机 水冲击 温度
分 类 号:TP29[自动化与计算机技术—检测技术与自动化装置]