水电厂发电机出口断路器解体故障分析  

Analysis on a Breakdown Failure of Generator Circuit Breaker in a Hydropower Plant

在线阅读下载全文

作  者:欧亮 刘守豹 韦昌伟 石桂学 OU Liang;LIU Shoubao;WEI Changwei;SHI Guixue(Datang Hydropower Science&Technology Research Institute Co.,Ltd.,Nanning 530007)

机构地区:[1]大唐水电科学技术研究院有限公司,广西南宁530007

出  处:《电力安全技术》2023年第2期33-35,共3页Electric Safety Technology

摘  要:发电机出口断路器起着控制机组与电力系统并列或解列的作用,广泛应用于电厂。以某700 MW发电机出口断路器解体故障为例,通过现场检查和分析,查明出口断路器解体根本原因为触头传动机构机械故障,并提出具体处置及维护建议以避免同类故障再次发生。Generator circuit breaker(GCB) is in charge of the paralleling and splitting control of units and electric power systems, which is widely applied in power plants. Taking a 700 MW GCB breakdown failure as example, by the field inspection and analysis, the root cause of the GCB failure is identified as that of the main drive mechanism of the GCB contact, and specific settlement and maintenance recommendations are put forward so as to avoid the recurrence of similar accidents.

关 键 词:发电机出口断路器 机械故障 解体故障 

分 类 号:TM561[电气工程—电器]

 