基于压管法的电缆分割导体直流电阻测试方法  

Test Method of Cable Segmental Conductors DC Resistance Based on Pressure Tube Method

在线阅读下载全文

作  者:张恒玮 黄玉兰 潘仁勇 刘涛 毛开裕 蒋东旭 ZHANG Heng-wei;HUANG Yu-lan;PAN Ren-yong;LIU Tao;MAO Kai-yu;JIANG Dong-xu(Sunway Co.,Ltd,Leshan 614001,China)

机构地区:[1]尚纬股份有限公司,四川乐山614001

出  处:《电工电气》2023年第3期43-46,共4页Electrotechnics Electric

摘  要:针对传统电缆分割导体直流电阻测试方法中测试结果准确度较低、分散性较大的问题,提出一种基于压管法的电缆分割导体直流电阻测试方法。该方法利用液压装置和铜管对电缆分割导体进行紧压定型,可有效减少股块或单线之间导体的接触电阻,提升直流电阻测试结果的准确性。实际测试结果表明,相比于传统方法,因为该方法能有效降低股块和单线之间导体的接触电阻,所以能提升测试结果的准确性,为电缆分割导体直流电阻测试提供了新的思路。The traditional cable segmental conductor DC resistance test method has disadvantages of low accuracy and large dispersion,so a new test method based on pressure tube method is proposed.It uses hydraulic equipments and copper tubes to compact and shape the cable segmental conductor,which can effectively reduce conductor contact resistance of strands or wires and increase the accuracy of DC resistance test results.The actual experiment shows that this method is able to decrease conductor contact resistance of strands or wires to improve the accuracy of the test results,providing a new idea for DC resistance test of cable segmental conductors.

关 键 词:分割导体 V型夹具 导体直流电阻 试样处理 压管法 

分 类 号:TM934.12[电气工程—电力电子与电力传动]

 