罗氏线圈灵敏度校准方法  被引量:2

Study on calibration method of roche coil sensitivity

在线阅读下载全文

作  者:陈建志 阮育娇 胡晓英 崔潼 Chen Jianzhi;Ruan Yujiao;Hu Xiaoying;Cui Tong(Xiamen Institute Of Measurement And Testing)

机构地区:[1]厦门市计量检定测试院

出  处:《上海计量测试》2022年第6期4-7,共4页Shanghai Measurement and Testing

基  金:厦门市市场监督管理局科技项目(XMSJ202206)。

摘  要:介绍了一种罗氏线圈灵敏度的校准装置及校准方法,采用高稳定大功率交变电流源,校准时通过电流比例标准和标准电阻I/U转换方式确定标准一次电流值,从而确保罗氏线圈灵敏度校准的有效性及准确性。分析罗氏线圈灵敏度校准过程的影响因素并对测量结果进行了不确定度评定分析。Roche coil is a kind of AC current measuring equipment,which has many advantages over traditional current measuring devices such as current transformer.It has convenient wiring,wide measuring frequency range and current range,etc.It’s widely used in power,petrochemical,new energy industries,especially in large current test and monitoring,high-frequency testing and analysis of applications.This paper introduces a calibration device and method of Roche coil sensitivity,which adopts high stable and large current source.Adopted I-U conversion mode determines the primary standard current by AC current ratio standard and standard resistance,so as to ensure the validity and accuracy of Roche coil sensitivity calibration.The impact factors of the calibration process are analyzed and the uncertainty of measurement results is evaluated.

关 键 词:罗氏线圈 灵敏度 电流比例标准 校准方法 不确定度分析 

分 类 号:TM933.1[电气工程—电力电子与电力传动]

 