作 者:胡静 王小红[1,2] 杨艳平[3] 杨合民[1,2] 梁绍泉[3] HU Jing;WANG Xiaohong;YANG Yanping;YANG Hemin;LIANG Shaoquan(State Grid Electric Power Research Institute,Nanjing 211106,China;NARI Technology Co.,Ltd.,Nanjing 211106,China;Shandong Taishan Pumped Storage Power Station Co.,Ltd.,Taian 271000,China)
机构地区:[1]国网电力科学研究院,南京211106 [2]国电南瑞科技股份有限公司,南京211106 [3]山东泰山抽水蓄能电站有限责任公司,山东泰安271000
出 处:《大电机技术》2023年第4期63-71,共9页Large Electric Machine and Hydraulic Turbine
基 金:国家电网有限公司总部科技项目(5100-202240496A-3-0-ZZ)。
摘 要:泰安抽水蓄能电站SFC系统自2005年投运以来,设备长时间运行,元器件老化严重,随着机组启动次数的增加,偶发性故障时有发生,需对其进行改造。通过动态模拟仿真试验平台,制定了系统的启动调试试验大纲,同时对SFC系统的控制逻辑进行了充分的验证。本文对泰安抽水蓄能电站静止变频启动控制系统改造进行了阐述,提出了单套输入、输出变压器接口下实现双SFC系统的启动控制技术,彻底解决了旁路刀闸故障引起的启机失败问题。针对现场提出了完整的启动控制调试试验方案,并创新性提出基于无旁路刀闸方式的启动技术,试验结果证明了改造后双系统运行的稳定性及可靠性,实现了双系统设备的冗余技术,为后续抽水蓄能电站国产化改造项目提供了可借鉴的经验。Since the SFC system of Taian pumped storage power station was put into operation in 2005,the equipment has operated for a long time,and the components are seriously aged.With the increase of unit start-up times,occasional faults often occur,so it needs to be reformed.Through the dynamic simulation experimental platform,a system start-up and debugging test outline is developed,and the control logic of the SFC system is fully verified.This paper expounds the transformation of static frequency converter starting control system of Taian pumped storage power station,and proposes a start control technology for implementing a dual SFC system under a single set of input and output transformer interfaces,completely solving the problem of startup failure caused by bypass switch faults.A complete start-up control commissioning test scheme is proposed for the site,and the startup technology based on the non-bypass knife switch mode is innovatively proposed.The test results prove the stability and reliability of the dual system operation after the transformation,realize the redundancy technology of the dual system equipment,and provide reference experience for the followup domestic transformation projects of pumped storage power stations.
关 键 词:静止变频器 SFC系统 双系统控制 无旁路刀闸 调试试验
分 类 号:TM921.5[电气工程—电力电子与电力传动]
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:3.148.185.226