作 者:颜龙[1] 王文强 赵雯筠 陈善求 Yan Long;Wang Wenqiang;Zhao Wenjun;Chen Shanqiu(Institute of Disaster Prevention Science and Safety Technology,Central South University,Hu'nan Changsha 410075,China;Goldcup Electric Apparatus Co.,Ltd.,Hunan Changsha 410205,China)
机构地区:[1]中南大学防灾科学与安全技术研究所,湖南长沙410075 [2]金杯电工股份有限公司,湖南长沙410205
出 处:《消防科学与技术》2023年第3期293-297,共5页Fire Science and Technology
基 金:湖南省高新技术产业科技创新引领计划(2021GK4032);国家自然科学基金项目(52276143)。
摘 要:通过氧指数测试仪、垂直燃烧测试仪和辐射锥测试分析了耐火电缆和普通电缆的护套层的燃烧性能,并结合电缆燃烧试验分析电缆数量和敷设间距对电缆燃烧性能的影响。结果表明:普通电缆护套层的极限氧指数(LOI)为25.5%并通过垂直燃烧V-0级测试,燃烧过程中存在明显收缩卷曲现象,无法有效保护内部线芯材料;而耐火电缆护套层的LOI达到34.5%,燃烧过程中能够形成致密的膨胀炭层,可有效保护内部线芯结构。电缆燃烧试验表明:电缆的火灾危险性随电缆敷设数量的增加而逐渐增大,随电缆敷设间距增加而逐渐减小。与紧密排列时相比,电缆敷设间距为电缆直径的2倍时耐火电缆和普通电缆的平均质量损失分别降低了87.1%和97.6%,平均炭化长度分别降低了92.6%和92.9%,电缆的火灾危险性最低。此外,与耐火电缆相比,普通电缆的火灾危险性受电缆敷设数量和间距的影响更大。The combustion properties of the sheath layer materials of fire-resistant cables and common cables were analyzed via oxygen index(LOI)tester,vertical combustion tester and radiation cone.Combined with cable tunnel model test,the influence of the quantity of cables and laying spacing on the combustion properties of two kinds of cables were investigated.The results show that the LOI value of the sheath layer materials of common cables is 25.5%,and it passes the vertical combustion V-0 rating,and there is obvious shrinkage curl phenomenon during the combustion process,it can not effectively protect the internal core material.The LOI of fire-resistant cable is 34.5%,and it can form a dense expanded carbon layer to protect the internal core structure effectively during the burning process.Cable burning test shows that the fire hazard of cables increases gradually with the increase of cable laying quantity and decreases gradually with the increase of cable laying spacing,among which the fire hazard of cables is the lowest when the cable laying spacing is 2 times of the cable diameter.Compared to the tight arrangement,the average mass loss of fire-resistant cables and common cables are reduced by 87.1%and 97.6%respectively,and the average char length was reduced by 92.6%and 92.9%,respectively.In addition,compared with fire-resistant cables,the fire hazard of common cables is more influenced by the quantity and spacing of cable laying.
关 键 词:耐火电缆 普通电缆 敷设数量 敷设间距 燃烧性能
分 类 号:X913.4[环境科学与工程—安全科学] TU541[建筑科学—建筑技术科学]
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:216.73.216.229