冷却塔填料及非均匀配水协同优化研究  被引量:6

Synergistic optimization study of cooling tower packing and non-uniform water distribution

在线阅读下载全文

作  者:王为术[1] 高明[2] 王明勇[3] 李陆军[4] 张振[1] 郭欣维 王杰[1] WANG Weishu;GAO Ming;WANG Mingyong;LI Lujun;ZHANG Zhen;GUO Xinwei;WANG Jie(College of Energy and Power Engineering,North China University of Water Resources and Electric Power,Zhengzhou 450045,China;School of Energy and Power Engineering,Shandong University,Jinan 250061,China;Xi’an Thermal Power Research Institute Co.,Ltd.,Xi’an 710054,China;China Institute of Water Resources and Hydropower Research,Beijing 100038,China)

机构地区:[1]华北水利水电大学能源与动力学院,河南郑州450045 [2]山东大学能源与动力工程学院,山东济南250061 [3]西安热工研究院有限公司,陕西西安710054 [4]中国水利水电科学研究院,北京100038

出  处:《热力发电》2023年第5期100-106,共7页Thermal Power Generation

基  金:国家自然科学基金项目(51776111);河南省科技攻关项目(172102310747)。

摘  要:为提升冷却塔的冷却性能,以北方某300 MW机组冷却塔为例,建立冷却塔三维数值计算模型,对比二分区及三分区不均匀填料对出塔水温的影响,确定最优半径分界点,并协同非均匀配水进行优化,分析不同优化方案对出塔内空气流速、塔水温、通风量的影响。结果表明:二分区及三分区非等间距填料下出塔水温分别为31.798℃和31.696℃,冷却性能提升;非等间距填料与非均匀配水的耦合优化显著提高了空气动力和温度场的均匀性;随着内区配水量的增加,水温和通风量均呈现先增加后减少的趋势;最佳内区配水量为50.0%,出塔水温为31.360℃通风量7122.8 kg/s;与26 mm和30 mm等距填料布置相比,协同优化后,出塔水温分别降低了0.768℃和0.830℃,冷却性能显著提升。In order to improve the cooling performance of cooling tower,this study takes a 300 MW unit cooling tower in the north as an example,establishes a 3D numerical calculation model of cooling tower,compares the effect of non-equal packing in two and three zones on the outlet tower water temperature,determines the optimal radius dividing point,and cooperates with non-uniform water distribution for optimization,analyzes the effect of different optimization schemes on the air flow rate,tower water temperature and ventilation volume in the outlet tower.The results show that the cooling performance is improved with the exit tower water temperature of 31.798℃ and 31.696℃ under the non-equally spaced packing in the second and third divisions,respectively.The coupling optimization of non-equally spaced packing with non-uniform water distribution significantly improves the uniformity of aerodynamic and temperature fields.With the increase of water distribution in the inner zone,the outlet water temperature and ventilation volume both show a trend of first increase and then decrease,and the optimal water distribution in the inner zone is 50%,and the outlet tower water temperature is 31.36℃ and ventilation volume is 7122.8 kg/s.Compared with 26 mm and 30 mm equidistant packing arrangement,after collaborative optimization,the water temperature of the tower is reduced by 0.768℃ and 0.83℃,respectively,and the cooling performance is significantly improved.

关 键 词:冷却塔 非等间距填料 非均匀配水 数值模拟 

分 类 号:TM621[电气工程—电力系统及自动化]

 

参考文献:

正在载入数据...

 

二级参考文献:

正在载入数据...

 

耦合文献:

正在载入数据...

 

引证文献:

正在载入数据...

 

二级引证文献:

正在载入数据...

 

同被引文献:

正在载入数据...

 

相关期刊文献:

正在载入数据...

相关的主题
相关的作者对象
相关的机构对象