检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
作 者:王玥明 卢经朝 庄大伟[1] 丁国良[1] Wang Yueming;Lu Jingchao;Zhuang Dawei;Ding Guoliang(Institute of Refrigeration and Cryogenics,Shanghai Jiao Tong University,Shanghai,200240,China)
机构地区:[1]上海交通大学制冷与低温工程研究所,上海200240
出 处:《制冷学报》2023年第3期111-118,共8页Journal of Refrigeration
摘 要:高热流密度电子设备发热功率日益增加,需要新的高效冷却技术保障其安全运行,采用大过冷度流体与微针肋结构结合的方式是提升冷却能力的一种新思路。本文实验观测了微针肋结构过冷沸腾现象,测试了不同过冷度(50、60、75、95℃)对表面传热系数与临界热流密度的影响,确定了大过冷度下微针肋结构相比光滑结构表面传热系数的强化比例,研究了微针肋结构过冷沸腾强化传热机理。结果表明:当热流密度超过200 W/cm^(2)时,微针肋结构过冷沸腾换热表面传热系数随过冷度增大而增大;微针肋结构临界热流密度随过冷度上升而上升,当过冷度由50℃升至95℃,临界热流密度由228 W/cm^(2)升至400 W/cm^(2)以上;微针肋结构表面传热系数均比同工况下的光滑结构表面传热系数大,微针肋结构的强化传热效果在大热流密度、大过冷度下更为显著,当热流密度为250 W/cm^(2)、过冷度为95℃时,强化比例为1.28。In response to the power increase in electronic devices with high heat flux density,new efficient cooling technologies should be developed to ensure the safe operation of these electronic devices.The application of micro-pin-fin structures under high-degree subcooled boiling is a promising way of enhancing the cooling capacity.In this study,subcooled boiling on a micro pin-fin surface was observed,and the effects of the subcooled temperature on the heat transfer coefficient and critical heat flux were measured.Moreover,the heat transfer coefficients of the micro-pin-fin structure were compared with those of a smooth surface,and the heat transfer enhancement mechanism of the micro-pin-fin structure was investigated.The results show that the heat transfer coefficient of the micro-pin-fin surface increases with an increase in the subcooled degree when the heat flux is greater than 200 W/cm^(2).The critical heat flux increases from^(2)28 W/cm^(2) to more than 400 W/cm^(2) when the subcooled degree increases from 50℃to 95℃.The heat transfer coefficient of the micro-pin-fin surface is always larger than that of the smooth surface under the same working conditions,and the effect of the micro-pin-fin surface is more obvious under high degrees of subcooling and high heat flux.The enhancement factor is 1.28 when the heat flux is 250 W/cm^(2) and the degree of subcooling is 95℃.
分 类 号:TB611[一般工业技术—制冷工程] TB69
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:3.128.153.31