作 者:Mohamed E.Ibrahim Amr M.Abd-Elhady
出 处:《High Voltage》2017年第2期129-135,共7页高电压(英文)
摘 要:This study presents a technique for power frequency AC voltage measurement.The proposed technique utilises a capacitor having a low capacitance in addition to a double wound Rogowski coil.This technique depends on capacitor current measurement using the double wound Rogowski coil.The voltage across the capacitor that connected in parallel with the system at which AC voltage is intended to be measured is reconstructed.The proposed technique is experimentally evaluated by designing the measurement system and using a digital signal processing board for the reconstruction processes.Moreover,the experimental results based on Rogowski coil measurements are compared with those obtained from reference techniques.Finally,the obtained results validate the efficacy of the proposed technique in power frequency AC voltage measurement.
关 键 词:ROGOWSKI DOUBLE CAPACITANCE