海上风电送出J型管段海底电缆载流量计算模型研究  被引量:6

Study on Calculation Model of Submarine Cable Ampacity in J-Tube Section of Offshore Wind Power Transmission

在线阅读下载全文

作  者:李根 杜志叶[1] 肖湃 郝兆扬 崔戎舰 Li Gen;Du Zhiye;Xiao Pai;Hao Zhaoyang;Cui Rongjian(School of Electrical Engineering and Automation,Wuhan University,Wuhan,430072,China;Central Southern China Electric Power Design InstituteCo.Ltd of China Power Engineering Consulting Group,Wuhan,430071,China)

机构地区:[1]武汉大学电气与自动化学院,武汉430072 [2]中国电力工程顾问集团中南电力设计院有限公司,武汉430071

出  处:《电工技术学报》2023年第13期3619-3629,共11页Transactions of China Electrotechnical Society

基  金:国家自然科学基金资助项目(51977152)。

摘  要:海上风电场送出线路从升压站穿出首先需经过散热环境较差的J型管段,目前针对该区段海底电缆载流量的计算主要采用数值模拟法,而三维流体仿真计算非常耗时,因此难以推广使用。该文基于基本热分析方法提出了J型管段海底电缆径向-轴向传热解析模型,考虑温度沿轴向分布的差异,实现J型管段海底电缆载流量的快速计算。在计及导体电阻率随温度变化情况下,利用数值仿真软件建立海底电缆J型管系统三维热-流耦合数值模型,并与径向-轴向传热解析模型进行了对比计算。最后基于两种方法分析了J型管外径、太阳辐射强度和环境温度对J型管段海底电缆缆芯最高温度的影响规律。结果表明,J型管段海底电缆缆芯最高温度与太阳辐射强度和环境温度存在明显的线性关系,而J型管外径与海水温度对J型管段海底电缆缆芯最高温度影响较小,且解析法与数值仿真计算结果误差在5%以内。该文所提出针对J型管段海底电缆载流量计算的解析法高效准确,具有较好的工程应用价值。The transmission line of offshore wind farm generally passes through the J-tube section with poor heat dissipation conditions,which is divided into three sections:platform section,tube air section and tube water section.The tube air section is often the weak point of ampacity of the submarine cable due to the closed air interlayer between the J-tube and the cable.There is no standard formula for calculating the ampacity of submarine cables in this laying section,which mainly depends on the numerical simulation.However,3-D fluid simulation is time-consuming.This paper proposes an analytical model of radial-axial heat transfer of submarine cables in J-tube section,which takes into account the axial temperature distribution difference of submarine cable conductors and realizes the rapid calculation of ampacity of submarine cables in J-tube section.Firstly,the radial thermal path model of the submarine cable in J-tube section is built according to the thermoelectric analogy method.The Nusselt number correlation formula is used to calculate the convection heat transfer coefficient between the submarine cable surface and the inner surface of J-tube.And the radiation heat transfer between the submarine cable surface and the inner surface of J-tube is considered.Secondly,the axial heat transfer of submarine cable conductor in J-tube section is approximated by the heat transfer model of medium cross-section straight rib,and the axial heat transfer model is built on the basis of its radial model.Finally,with the radial-axial thermal path model of the J-section submarine cable,the conductor temperature distribution of the J-tube submarine cable under the given current load can be quickly calculated by the dichotomy method.Taking high voltage DC submarine cable as an example,a comparative calculation is carried out with the analytical model and the 3-D numerical model.The results show that when the length of tube air section is 5 m,the error between the maximum temperature of the conductor calculated by the axial heat transf

关 键 词:海底电缆 J型管 解析法 数值模拟 载流量 

分 类 号:TM247[一般工业技术—材料科学与工程]

 

参考文献:

正在载入数据...

 

二级参考文献:

正在载入数据...

 

耦合文献:

正在载入数据...

 

引证文献:

正在载入数据...

 

二级引证文献:

正在载入数据...

 

同被引文献:

正在载入数据...

 

相关期刊文献:

正在载入数据...

相关的主题
相关的作者对象
相关的机构对象