作 者:李秋思 张讥培 兰宁远 张照真 LI Qiusi;ZHANG Jipei;LAN Ningyuan;ZHANG Zhaozhen(Pingdingshan Electric Power Company,State Grid Henan Power Company,Pingdingshan 467000,China)
机构地区:[1]国网河南省电力公司平顶山供电公司,河南平顶山467000
出 处:《电工技术》2023年第10期203-205,共3页Electric Engineering
摘 要:介绍了一起110 kV主变低压母线单相接地导致低压进线开关烧毁的事故。通过主变低后备保护动作分析,阐述了事故发展过程和原因。结合变电站低压设备接线结构对低后备保护动作逻辑进行探讨,提出事故应急处理建议,为调度员快速恢复送电提供参考。An accident in which the low-voltage inlet switch burned out due to single-phase grounding of the low-voltage bus of the 110 kV main transformer is introduced.Through the analysis of the low-voltage backup protection action of the main transformer,the development process and causes of the accident are expounded.Combined with the wiring structure of low-voltage equipment in substation,the operation logic of low backup protection is discussed,and suggestions for emergency handling of accidents are put forward,which provides a reference for dispatchers to quickly resume power transmission.