Impedance Analysis of Grid Forming Control Based Modular Multilevel Converters  被引量:3

在线阅读下载全文

作  者:Rongcai Pan Guangfu Tang Shan Liu Zhiyuan He 

机构地区:[1]China Electric Power Research Institute,Beijing 100192,China [2]State Grid Smart Grid Research Institute,Beijing 102209,China

出  处:《Journal of Modern Power Systems and Clean Energy》2023年第3期967-979,共13页现代电力系统与清洁能源学报(英文)

基  金:supported by the State Grid Corporation Science and Technology Project(No.5100-202158335A-0-0-00).

摘  要:Grid-forming control(GFC)is promising for power electronics based power systems with high renewable energy penetration.Naturally,the impedance modeling for GFC is necessary and has gained significant attention recently.However,most of the impedance analyses for GFC are based on a twolevel converter(TLC)rather than a modular multilevel converter(MMC).MMC differs from TLC with respect to its dominant multi-frequency response.It is necessary to analyze the impedance of GFC-based MMC owing to its superiority in highvoltage direct current(HVDC)transmission to interlink two weak AC systems with high renewable energy penetration.As the main contribution,this paper presents the AC-and DC-side impedance analyses for the GFC-based MMC with both power and DC voltage control using the harmonic transfer function(HTF),and compares the impedances of GFC-based MMC and TLC.It is inferred that although the impedance is mainly influenced within 200 Hz,the instability still could occur owing to negative resistance triggered by relatively larger parameters.The difference in AC-side impedance with power and DC voltage control is not apparent with proper parameters,while the DC-side impedance differs significantly.The generalized Nyquist criterion is necessary for AC-side stability owing to the relatively large coupling terms under GFC.Moreover,the coupling between AC-and DC-side impedances is noneligible,especially considering the DC-side resonance around the system resonant peak.The effects of parameters,system strength,and virtual impedance on the impedance shaping are analyzed and verified through simulations.

关 键 词:Sequence impedance modular multilevel converter(MMC) grid-forming control(GFC) harmonic transfer function generalized Nyquist criterion 

分 类 号:TM46[电气工程—电器]

 

参考文献:

正在载入数据...

 

二级参考文献:

正在载入数据...

 

耦合文献:

正在载入数据...

 

引证文献:

正在载入数据...

 

二级引证文献:

正在载入数据...

 

同被引文献:

正在载入数据...

 

相关期刊文献:

正在载入数据...

相关的主题
相关的作者对象
相关的机构对象