分级处理空调送风的地下水源热泵系统性能研究  被引量:1

STUDY ON PERFORMANCE OF GROUNDWATER SOURCE HEAT PUMP SYSTEM WITH GRADED TREATMENT OF SUPPLY AIR

在线阅读下载全文

作  者:陈枫 谈莹莹[1] 李修真 王林[1] 王占伟 连梦雅 Chen Feng;Tan Yingying;Li Xiuzhen;Wang Lin;Wang Zhanwei;Lian Mengya(Institute of Building Energy and Thermal Science,Henan University of Science&Technology,Luoyang 471023,China)

机构地区:[1]河南科技大学建筑能源与热科学技术研究所,洛阳471023

出  处:《太阳能学报》2023年第6期178-185,共8页Acta Energiae Solaris Sinica

基  金:国家自然科学基金(51876055);河南省高校科技创新团队(22IRTSTHN006);河南省重点研发与推广专项(科技攻关)(212102310327)。

摘  要:针对传统地下水源热泵空调(CGWHP)系统能耗偏高的缺陷,提出一种新型分级处理空调送风的地下水源热泵(NGWHP)系统,其特点是利用地下水预处理新风后,二级利用地下水承担热泵机组的冷凝热,达到显著降低热泵机组能耗的目的。运用热工学理论建立NGWHP系统稳态仿真数学模型,在VC++环境下编写程序并模拟供冷模式下NGWHP与CGWHP系统的性能,比较分析地下水对两种系统性能的影响,并搭建实验装置进行验证。结果表明:NGWHP系统的能耗显著低于CGWHP系统。地下水供水温度下降或流量增大,两种系统的能耗均呈线性下降趋势。新风比为33%,地下水温从24℃降至15℃时,NGWHP系统的能耗较CGWHP系统平均低40.56%;地下水流量从1800 kg/h增至2300 kg/h时,NGWHP系统的能耗平均降低42.27%。实验结果与模拟结果吻合较好,二者误差在±13%以内。研究结果可为NGWHP系统的优化设计和运行调控提供理论指导。In view of the high energy consumption of conventional groundwater source heat pump with air-conditioning(CGWHP)system,a novel groundwater source heat pump system with graded treatment of supply air(NGWHP)system is proposed.The groundwater is used to pretreat fresh air and bear the condensation heat of heat pump units,so as to significantly reduce the energy consumption of heat pump units.The steady-state simulation mathematical model of NGWHP system is established by using thermal theory,and the program on the cooling performance of NGWHP and CGWHP systems is made in VC++environment.The influences of groundwater on the performance of the two systems are compared and analyzed,and an experimental setup is built to verify the simulated values.The results show that the energy consumption of NGWHP system is significantly lower than that of CGWHP system.As the temperature of groundwater supply decreases or the flow rate increases,the energy consumption of the two systems shows a linear downward trend.When the groundwater temperature decreases from 24℃to 15℃with 33%fresh air fraction,the energy consumption of NGWHP system is 40.56%lower than that of CGWHP system on average.When the groundwater flow increases from 1800 kg/h to 2300 kg/h,the average energy consumption of NGWHP system is 42.27%lower than that of the CGWHP system.The experimental results are in good agreement with the simulation results,and the relative errors between the two results are in the range of±13%.The results provide theoretical guidance for the optimization design and operation control of the NGWHP system.

关 键 词:地下水源热泵 送风 预冷器 分级处理 稳态模型 能耗 

分 类 号:TU831[建筑科学—供热、供燃气、通风及空调工程]

 

参考文献:

正在载入数据...

 

二级参考文献:

正在载入数据...

 

耦合文献:

正在载入数据...

 

引证文献:

正在载入数据...

 

二级引证文献:

正在载入数据...

 

同被引文献:

正在载入数据...

 

相关期刊文献:

正在载入数据...

相关的主题
相关的作者对象
相关的机构对象